Earthing vs. Bonding: What's the Difference?

  Переглядів 64,926

eFIXX

eFIXX

День тому

Electricians often get confused between earthing and bonding of an electrical installation. James Curnow explains the differences and the key references within the UK wiring regulations BS7671.
What is the difference between exposed conductive parts and extraneous conductive parts. What is equipotential bonding?
🕐 TIME STAMPS 🕕
======================
00:00 What is bonding what is earthing
00:16 What does BS7671 say
01:02 Exposed conductive parts
01:23 Fault conditions
01:46 Bonding
02:37 Extraneous conductive parts
02:54 TN supply
03:13 Same potential
03:49 Pipework passing through a building
04:57 Supplementary bonding
05:31 Omitted supplementary bonding
06:01 Supplementary bonding is required
================================
🔦 More electrical Q&A videos from eFIXX
👉 www.efixx.co.uk/electricians-...
================================
🆕 FREE CPD Learn about new applications, regulations and best practices with our FREE CPD modules. - New modules are released monthly, covering everything from surge protection to lighting.
👉hub.efixx.co.uk/CPD​
================================
📍SUBSCRIBE TO THE CHANNEL
eFIXX helps electricians, electrical contractors, building services engineers, and electrical apprentices. So if you've been on the tools for years or just starting your electrical journey, we'll help you stay up to date with the latest regulations and developments in the electrical industry.
👉hub.efixx.co.uk/youtube-subscribe
========================================
📺 NEW TO THE CHANNEL?
Watch our essential videos playlist
👉 hub.efixx.co.uk/essentials
=========================================
#efixx #earthing #bs7671

КОМЕНТАРІ: 47
@sergiofernandez3725
@sergiofernandez3725 Рік тому
Earthing vs. Bonding. I spoke to Pete the Plasterer and he gave me a different answer.
@yaffajaff
@yaffajaff Рік тому
I spoke to a kinky gardener. He also gave me a different answer!
@quinsboy7578
@quinsboy7578 Рік тому
Many thanks for this, I like the delivery style which is easy on the ear, technically correct and very userul.
@efixx
@efixx Рік тому
Thanks for the feedback. 😊
@gbelectricks
@gbelectricks Рік тому
Welcome to efixx James, looking forward to more content👊
@davehunt5706
@davehunt5706 Рік тому
A lot of info delivered, well done and thank you
@efixx
@efixx Рік тому
Glad it was helpful!
@GSHElectrical
@GSHElectrical Рік тому
Fantastic content James 🦾
@efixx
@efixx Рік тому
Cheers Gaz. 😊
@UsualYaddaYadda
@UsualYaddaYadda Рік тому
Thank goodness that the tongue twister BS7671 is written in the description text... it's impossible to ascertain from any of the occasions that it is spoken... "be'esevixevven-one" good, clear, informative video aside from that. Thanks.
@davidblyth5495
@davidblyth5495 Рік тому
An interesting talk on the subject. My professional work is on weapons systems which included electronics. Earthing is significantly more complex due to the high frequencies and the risk of potential differences over conductors at distances over a portion of a wavelength of the frequencies used in the system. This could induce noise which affects the correct function of the circuitry, particularly digital circuits. So there may be an earth and several common bonding points to address this. We specify bonding quality as resistance/conductivity eg mOhms. I have seen poor bonding in a power circuit produce heat till the connection was damaged by heat and then arcing. This is of particular importance where the system is aboard a moving platform eg aircraft, ship of land vehicle.
@Dog-whisperer7494
@Dog-whisperer7494 Рік тому
Welcome to eFIXX James Nice explanation on earth bonding. Well done 👍
@efixx
@efixx Рік тому
Thanks Sean. 👍
@x1BULLETfromABOVE1x
@x1BULLETfromABOVE1x Рік тому
Recap Earthing - for Exposed conductive parts that are part of the installation (metal switches) Equipotential bonding - for extraneous conductive parts that are not part of the installation but could become live under fault conditions (gas pipes)
@grahamheath9957
@grahamheath9957 Рік тому
This topic always makes we wonder why we don’t just have an earth rod at every house as effectively (at least in my view) extraneous conductive parts perform broadly the same function and surely there would be a lot of advantages to doing this, and I would have thought it would prevent PEN faults.
@arcadia1701e
@arcadia1701e Рік тому
I have always wondered this myself, why doesn't every property have a TT rod just incase.
@deang5622
@deang5622 Рік тому
The correct way to deal with a PEN fault is to use a PEN fault detection device. Not install a second earthing method. And TT doesn't make a good earth. The resistance is greatly variable and higher than other methods.
@timothydixon2545
@timothydixon2545 Рік тому
So now you’re suggesting that you megger every wire lol
@Pgan803
@Pgan803 Рік тому
Thank you for a great video. Q1) Would Bonding Works if the separate parts are connected to separate earthing rods, in cases where large distance makes running a cable back to the other parts costly or impractical, compared to running a cable to a new separate Earth Rods. Since earth potential is zero, there will be no cable link between Earth Road 1 to 2 to 3.. etc 2) It would be clearier if more pictures examples be shown for Bonding cases
@yasuke1709
@yasuke1709 25 днів тому
What is meant by potential? I'm not understanding the concept. I understand that extraneous conductive parts can be dangerous unless earthed, but when they become the same equal potential, what does that mean? Does it just mean they have the same eletrical charge or something?
@Jack-zr4lm
@Jack-zr4lm Рік тому
Great video, Could you do a video explaining about the neutral conductor?
@timothydixon2545
@timothydixon2545 Рік тому
They don’t have a neutral incoming on their residence’s they use it on 3 phase systems
@jsb7546
@jsb7546 Рік тому
​@Timothy Dixon wth are you talking about of course they have nuetrals in their residence you need to not for everything here in the us we can often use split phase for 240 instilations 120 volt phase to ground/neutral and 240 phase to phase or should it be leg to leg sense it's all one phase just with the nuetral tapped in the middle of the Transformer. But ya you need a nuetral for most cases because of unbalanced loads.
@skabbymuff111
@skabbymuff111 Рік тому
Very informative, thanks.
@l3d-3dmaker58
@l3d-3dmaker58 Рік тому
im always confused because where i live, ground isn't provided to you, you have to put in a grounding rod and your neutral never connects to "your" ground (they're grounded only at the transformer). so we only have "one ground" that connects *every* device, pipe and outlet in the house to the grounding rod so that in the case of a fault, it all dumps there, no need for equipotential bonding as all "ground" in outlets or pipes are at 0v respective to the earth
@100tinsoldiers
@100tinsoldiers Рік тому
That’s a TT system, the fault isn’t dumped into the ground the ground is used as the fault path back to the star point of the transformer, the problem with a TT system is getting a low enough resistance back to the transformer, that’s why you then need RCDs
@olivertaylor4779
@olivertaylor4779 Рік тому
If something is metal just make sure it's connected to the earth 🌎 with a green and yellow wire.
@Sam-cl9lg
@Sam-cl9lg Рік тому
How do we get 100 and 48 volts at 3:14?
@brianwood5220
@brianwood5220 Рік тому
I would say it's probably an estimate and quite a good one I think.
@efixx
@efixx Рік тому
It's explained in detail in this video. ukposts.info/have/v-deo/qYiYmn2MsKOgzok.html
@ConorNoakes
@ConorNoakes Рік тому
It's the potential difference between different parts of the ground. It looks like they're trying to show the potential difference from the supply substation, etc. to the point the person is standing and from where the person is standing to both the point of supply (Meter, etc.) and to the extraneous metal coming out of the ground that has been bonded (they are standing in the middle as far as the potential difference shows). I'm not sure on this but I would suspect they've chosen 48V as the standard ELV safe-touch limit is
@oal2928
@oal2928 Рік тому
Pre watching: earthing: wire goes all the way back to earth block, bonding : the connection can be lost if x item bonded to it gets removed= losing its earth.
@mikeeb290
@mikeeb290 Рік тому
I think it was a good effort, but the clear difference has not been established to me. I understand "extraneous" aspects of the installation but the example above (especially the flat with the water main line) did not help- the excessive use of the word and not a more drawn out explanation if why that was considered part of the installation when you stated the ground on the 1st part of the flat was not considered part of the installation could have provided a better explanation. After all, by adding a ground you are making it part of the installation. Perhaps maybe explaining a clearcut definition of an installation would have been better first. Again, it was a nice shot but it was missed ( at least to me).
@Tryingtimes007
@Tryingtimes007 Рік тому
Hi James welcome to the “dark side” of electrics.
@efixx
@efixx Рік тому
He'll help shine a light into it. 😂
@Tryingtimes007
@Tryingtimes007 Рік тому
😆
@jayantvm
@jayantvm Рік тому
Why earth provided a return path to electric current ?
@channelI748
@channelI748 Рік тому
At equal voltage etc but I wouldn't like to test it.
@Dog-whisperer7494
@Dog-whisperer7494 Рік тому
Wow Joe Robinson has been pushed aside. Will regulation corner continue with Joe ?
@efixx
@efixx Рік тому
😂 Fair point, maybe I should hand it over, tune in tomorrow to find out...
@Dog-whisperer7494
@Dog-whisperer7494 Рік тому
@@efixx don’t you dare
@Dog-whisperer7494
@Dog-whisperer7494 Рік тому
@@efixx no one I mean no one can or could ever replace Joe on regulation corner. There’s only room for one regulation Boffin at regulation corner. And that’s Joe Robinson.
@gabor.nadudvari
@gabor.nadudvari Рік тому
I would like Joe Robinson back. Sorry I hardly understand James.
@linuxgaming69
@linuxgaming69 Рік тому
So it's the same. It's all connected to earth.
@Newit2
@Newit2 Рік тому
My neighbour is a poor pensioner skint her light in the bathroom was dead.so as a favour I fitted a new one there were 5 wires into the light straight away I told her she needs the wall fan rewired as there was no isolation switch and they were using the c.p.c. as a switched live and the outside light had no cpc on it.I put it all back together as it was the only way to get out the house she promised she would get it fixed proper,it had been like that for 10 years I checked the fan case for live it wasn’t.What do you do leave her in the dark I tried disconnect the fan and light No No it’s been working for 10 years it’s OK haha. It was a builder that fitted it in the first place I just did like for like.
@user-vs5fi2vy3h
@user-vs5fi2vy3h 5 днів тому
Worse explanation design to confuse students
Understanding Earthing Arrangements - TNCS, TT, TNS
5:59
eFIXX
Переглядів 44 тис.
Earthing & Bonding - Part 1 : Earthing
24:56
John Ward
Переглядів 186 тис.
Ages 1 - 100 Decide Who Wins $250,000
40:02
MrBeast
Переглядів 111 млн
Where Does Grounded Electricity Actually Go?
19:36
Practical Engineering
Переглядів 4,7 млн
What is Electrical Bonding? Bonding VS Earthing!⚡
6:05
Axis Electricals
Переглядів 12 тис.
Electric Wiring in Italy - You Won't Believe What They Do!
13:09
DO YOU NEED TO EARTH BOND PLASTIC WATER PIPES?
6:08
eFIXX
Переглядів 119 тис.
What is Ground? Earth Ground/Earthing
9:27
RimstarOrg
Переглядів 3,1 млн
How to correctly terminate bonding straps - life hack. Also covers easy clamps from AM2
20:07
Pure Electrical Training - by Adrian Davey
Переглядів 13 тис.
BS951 Clamps - Connecting Bonding Conductors to Metallic Pipes
15:08
Difference between grounding, earthing and bonding with examples
5:39
The Engineering Power
Переглядів 9 тис.
Клавиатура vs геймпад vs руль
0:47
Balance
Переглядів 351 тис.
NOTHING PHONE 2A - НЕОБЫЧЕН ВО ВСЕМ!
30:39
DimaViper
Переглядів 52 тис.
Зачем вы показываете ноутбук в аэропорту?✈️
0:29