This tutorial show how to carry out earth resistance test for commercial and resident building . Proper setting is importance for getting the better and accurate test result .
КОМЕНТАРІ: 227
@muhdyunus38943 роки тому
Video paling sng difahami...tq sgt2
@MrSyahryzal2 роки тому
Mudah untuk difahami... Lama mencari video earthing test untuk menambah ilmu. Terima kasih boss
@kalamsa7445Рік тому
Without much noise around, explained in a simple practical way...Thanks Rictor
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@castertroycabillar28632 роки тому
Thanks for this very informative vedio. More power.
@PbaY.3 роки тому
mantap tutorial nya .👍👍🌟🌟🌟
@o-techtips38712 роки тому
Thank you very much for your sharing very informative tips☺️
@yghiduppastimatikelak88542 роки тому
Good job ...thanks for sharing..
@marchomeautorepairs2 роки тому
Keep up the good work
@foonglikwei39132 роки тому
This teaching very useful and very easy to understand. Thanks and appreciate it 😊
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@salumhongo39559 місяців тому
You demonstrate this critical task to look easily, Thank you very much a learn a lot through your video.
@fje19487 місяців тому
The video I was looking for! Excellent explanation of the test. Thank you so much! Ps: The background music is pleasant and appropriate!
@ohhappyday15482 роки тому
thanks to your efforts, it is very helpful .. thank you..
@manjunathamanju62043 роки тому
Thank you Sir this video very useful for all Electrical engineers
@kirotomato73163 роки тому
easy to understand,thank you sir for wharing the information for us
@ahmedbelazi231811 місяців тому
Thank you for the effort made in the video.... I have a question... Is it true that the yellow wire is supposed to be an extension of the red wire, meaning on one line to give the reading... Why change in yellow only and should it be changed in red? ??
@electroboy36078 місяців тому
Good job..🎉 im practical test
@kanthasamymuthusamy739Рік тому
Simple explainations.Easy to underdstand
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@ofwj-ddah10 місяців тому
Thanls for sharingbthis video. It helps me a lots
@MrOner072 роки тому
very easy to follow... you earned a subscriber!❤️😊
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@joselitodupaya20923 роки тому
Thank you sir sa video
@angelosrcayabyab69522 роки тому
thanks for sharing
@sanjeevraghav3700Рік тому
Appreciate 👌👌you have done share gr8 experience with kyoritsu instrument 💐 This is sanjeev raghav from kyoritsu
@rictorrictor888Рік тому
Thank too .kyoritsu always the great equipment ..
@30mAkillsРік тому
This method is not FOP.
@william56242 роки тому
Very good👍🏻
@sanjeevraghav3700Рік тому
Very nice vedio 👌👌kudos to your effort 🙏🙏👌
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@iranweranga22510 місяців тому
Is there a specific number of times that earth resistance testing should be done for a specific area? (like number of times per meter squard)
@akilagayan6533Рік тому
Good work 👍
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@solomonnyaga70187 місяців тому
Does it mean now the earth resistance is perfect?
@CrisBoy4109 місяців тому
video excelente parabens , abraços do Brasil .
@nathan37141Рік тому
Thank you Engineer
@gabus1956Рік тому
Thank from Hungary
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@fazrulchanneltv91572 роки тому
Tq Sir. Clear and easy to undrstand. This place is like "Bukit Bendera" 😅
@rictorrictor8882 роки тому
Yes bro..bukit bendera..tqvm
@pankajraina4832Рік тому
Good sir 👍
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@user-ic5re6so6e2 роки тому
Thank you, sir
@francisrayang8052 роки тому
Hi sir. You did a very informative video thanks. I've a question for you.In the video you did the test on a big compound. I'm in a terrace house and the compound is very limited. I can't pull the yellow and red cable that long..only 3-4 meters to the nearest soil. Will it affect the reading? Please advice thks.
@rictorrictor8882 роки тому
In that situation ..You can try nearest area to ground the spike ..
@rictorrictor8882 роки тому
in that situation ..yes..
@30mAkillsРік тому
You have to maintain distance. Please read my other comments. Get permission from neighbours.
@jillferrer6135Рік тому
thank you sir..
@sahayaxaviersahayaxavier32173 роки тому
Salute sir
@redbirdgaming79052 роки тому
Thank you very much sir Many Thanks
@fauzibafana90892 роки тому
Can i know whether before the individual earth rod being tested you have to remove the connection of the earth rod from the rest.
@gniraj8501Рік тому
I am also have same question.
@30mAkillsРік тому
Yes it should be disconnected from service. If the voltage is more than 10 it will destroy the meter and also give false reading. Please read the user manual reg the max voltage limit that the meter will work safely in energised service without disconnection.
@muhdsolihin2641Рік тому
should be disconnecting earth cable from house to ground chamber first. so you will get the purest ground resistance.
@pankajmishra43Рік тому
Hiiii... You mean, first disconnect the earth cable from earth pit?? OR Can we shutdown the entire system before measuring earth resistance?? Pls guide
@Sim_TibyРік тому
Disconnect the earth cable.
@DiReal_DonclassyРік тому
Of course he must have done that before starting the test otherwise the resistances of home equipment will distort the result
@anthondiyРік тому
Thank you sir sa video another learning for earthing system
@arturotakuma4742Рік тому
excelent ¡¡¡
@fidelcatsro6948Рік тому
if we had no access to such equipment will adding more grounding rods to the ground all connected together potentially reduce the earth resistance?
@rictorrictor888Рік тому
Yes.
@fidelcatsro6948Рік тому
@@rictorrictor888 🐱👍🏿
@matsetizar6512 днів тому
when lightning strikes the earth doesn't the surge enter the house via the earth wiring? If so isn't it dangerous, probably better not to have any earthing system at all?
@gohpoikheng6030Рік тому
May i know why the cable for current is longer than the voltage?
@raemondbradford1629Рік тому
When current is injected into the earth, then the voltage will change around the location of injection. The voltage reference cable spike needs to be some distance from the points where current is injected or removed, in order to try and find a location with minimal disturbance of earth voltage potential.
@wazzer52935 місяців тому
Sir, how 1). If earth got voltage, what is the next action.. 2). When to use the setting mode 200 & 2000? Apprecite ur answer
@jhunedOz18Рік тому
Conclusion of 1.62 ohms? Meaning of that value? Is there a range passing value? I'd like to know.
@sanjeevraghav3700Рік тому
It means your earth grounding is perfect, anything less than 5ohm always consider perfect earthing as per indian standard 🙂
@svh61952 роки тому
Thanx!!
@vlogsidah893 роки тому
Mantap tuan,done support ya,maaf lewat.. 🙏🙏
@KGL1012932 роки тому
Hi, I have a Kyoritsu 4105A unit too, and I am getting "1. . ." reading at 20 ohm dial, who do you think is the problem, and how to fix this? Thank you.
@deutroitcity2 роки тому
It's over limit. U need to dial up the limit. Cannot use 20ohm. Because the reading is above 20 ohm
@nasiadomary4893Рік тому
How about if the reading is 25ohms What can i do to get less than 5Ohms?
@30mAkillsРік тому
@@nasiadomary4893 1. If possible increase the depth of electrode. 2. Insert another electrode at a distance of at least twice the buried depth of 1st electrode and link both at top. Eg.: If 1 st electrode buried depth = 3 M then second electrode should be installed at a distance of minimum 6 M away and both should be linked with wire or strip at the top. 3. Wet the pit by watering because dry earth is a bad conductor. Note : Chemical electrodes are fraud work. Hope all this helps.
@nasiadomary4893Рік тому
@@30mAkills Thanks🙏🙏
@siralexivan20063 роки тому
well done
@rictorrictor8883 роки тому
Tqvm
@DaBlackTradesManРік тому
I have to perform this same test but outside of the building is all concrete, a shower room will be built in the basement but first the neutral to earth voltage needs to be tested, so how would I go about this?
@frankkennedy7831Рік тому
you silly person. what sort of system are you on?
@30mAkillsРік тому
Check with normal clamp or multimeter in volts mode between earth and neutral of any 3 pin socket connected to that service. The voltage value should be below 2. Hope this helps.
@fje19487 місяців тому
@@frankkennedy7831 Perhaps you are the silly person making such an inappropriate comment! 🤢
@prabhus41372 роки тому
Hi sir I have a doubt. Could you please tell me the difference between 2 point, 3 point method. In megger it has 4 terminals C1, C2, P1, P2. how to measure earth pit resistance?
@30mAkillsРік тому
Short C1 and P1 and connect to electrode under test. P2 is for potential and C2 is for current spike. This is known as 3 point or Fall of Potential method. 4 terminals method is for testing soil as per Wenner method. This is for civil guys and not for electrical guys. Reg 2 point earth pit resistance testing: In India we don't/cant use this method because our public water supply is thru PVC pipes which is non conductor. Hope this helps.
@leomarbecilla2785Рік тому
hi sir. how do you perform it in a building where there is no earth ground to put the spike?
@rictorrictor888Рік тому
Extent green wire..
@rictorrictor888Рік тому
For condo there should have main electrical grounding
@dakwahislamcn63903 роки тому
Lanjutkan
@bornstar98972 роки тому
thanks
@anthonykihanga2881Рік тому
Thanks alot
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@bundaajhalah3 роки тому
Hadir nyimak 👍
@rictorrictor8883 роки тому
thank you so much
@neilblenkinsop2613Рік тому
To individually test the earth rod disconnect tape from earth rod
@surendrakverma555Рік тому
Good 🙏🙏🙏🙏🙏
@30mAkillsРік тому
Shifting potential spike towards right and left is wrong.
@dumindathusuth2026Рік тому
❤
@castertroycabillar28632 роки тому
Sir what is the porpuse for higher ohms setting.is it same result as 20ohms setting.thanks
@rictorrictor8882 роки тому
Yes..same.
@30mAkillsРік тому
For soil testing and also in hill areas.
@igorsmirnoff8578Рік тому
Будьте любезны,выложите такое же видео с прибором KEW 4106,спасибо!!!
@niezam17292 роки тому
Jika persekitaran rumah tamn agak sukar nk ambil bacaan,sb permukaan tanah @ berturap simen Dan jalan tar. 1- minutes 6.15 mase kita clamp wayar di electrod bumi.yg seeloknya copper tape @ cable incoming perlu ditanggalkan @ tidak semasa nak ambil bacaan.klu sye lihat Tuan x buka ..
@nasrulhelmeihalimppksistem74322 роки тому
kalau kawasan tar @ bersimen, boleh guna metal screen @ earthing mat. letak pada jarak yg ditetapkan & siram dgn air jd blh buat measurement
@japhethm61033 місяці тому
What readings should tell me that the resistance is not okay please
@rictorrictor8883 місяці тому
depend on local regulation ..as lower as possible. .below 10ohm
@azleeman3 роки тому
Saya nak tanya, bukankah testing dibuat semasa pemasangan rod sahaja (sebelum kita sambungkan dengan earth DB atau sebelum sambung ke perlindungan kilat)
@rictorrictor8883 роки тому
Kedua2 nya boleh ..sebelum dan selepas ..Sebenarnya Cooper tape itu bukan utk pelindung kilat..
@yosuaabimo93794 місяці тому
Test ini apakah harus saat listrik off?
@stanleyozoilo1587Рік тому
What is the accurate value for best low resistance using Megger machine
@rictorrictor888Рік тому
0 ohm
@30mAkillsРік тому
@@rictorrictor888 Practically not possible. Is earth full of gold?
@fje19487 місяців тому
@@rictorrictor888 I wish 😂
@wtnyambizi9876Рік тому
What about the distance btn the spikes does it matter !?
@anthonykihanga2881Рік тому
5 meters up to 10 meters it depends on soil type
@30mAkillsРік тому
Thumb rule for current spike distance from electrode = Minimum 8 to 10 times the buried depth of earth electrode. Eg., If earth electrode is 3 M long then C spike should placed about 24 to 30 M distance. This is to avoid '"zone of influence"' factor. Most manufacturers wont tell this because the distance will affect their tester sales in city and town areas where space is congested. So they suggest 5 M and 10 M which will not yield correct value. I challenge Kyoritsu in this matter.
@fje19487 місяців тому
@@30mAkills Thank you for this comment - can you please provide some formal references to confirm y you our comment - Thank you!
@lonedragon44102 роки тому
Below 5ohm is acceptable right?
@rictorrictor8882 роки тому
Yes
@wilsonloo85763 роки тому
Hi Rictor , may i know how to know the result is good or bad? Many Thanks
@rictorrictor8883 роки тому
low in reading is the batter .must below 10ohm.some time we can get 0 ohm. that the best..
@octaviohurtado27792 роки тому
It depends on your country standards. But the Best is the nearest to 0 ohms which is imposible to get 0 ohms. Also there are many methods to make the measurraments, it depends on your country standards too.
@loveandpeace594Рік тому
thanks :)
@30mAkillsРік тому
Shifting potential spike in perpendicular ( left and right)direction is not correct.
@aruquest253 роки тому
The green wire is for?
@rictorrictor8883 роки тому
electrode wire..
@olegkotletov78573 роки тому
green wire is for grass. grass is green. make sense right? put green wire on grass and see resistance of grass. grass is green, green wire is green too. make sense right? right.
@ericmunkanta296426 днів тому
Why is the leads in the same line
@Bestofthebest3837 днів тому
I had an exams question in college how to do earth rod test . I didn’t pass it 😢
@islammaidul6999Рік тому
Overall resistance how is it calculation sir
@rictorrictor888Рік тому
Total of test 1 ,2 ,3 then / by 3..it show on video min 13.20
@muhammadaresyamilbinazman7935Рік тому
Tumpang tanya, kan ada 20ohm, 200ohm, dan 2000ohm. Yang tu nak laraskan berdasarkan faktor apa ye?
@fidelcatsro6948Рік тому
dasarkan 20ohm setting
@AutodidactEngineerРік тому
The test should be done preferably during the driest season to prevent moisture from ruinning your values!
@File-TransferМісяць тому
I have a question, engr. Why is it required in the earth resistance tester manual to damp the surroundings?
@AutodidactEngineerМісяць тому
@@File-Transfer I don't know about that
@junsmackalbos456510 місяців тому
Sir the result you shown is that good or bad grounding
@rictorrictor88810 місяців тому
Good ..under 10 ohm
@junsmackalbos456510 місяців тому
Thanks sir......
@yusufsupyan99403 роки тому
Luar biasa kawan Videonya. Sudah saya kirim Bungkusan komplit dan,paten, durasipun Aman. Sesuai undangan. Ditunggu Amanahnya ya..
@rictorrictor8883 роки тому
Ya udah juga..terima kasih..
@kennedymutuku8950Рік тому
Hello Sir,what if the result is above 10,let say 50..how can you improve this to 5?
@AutodidactEngineerРік тому
Use a combination of vertical and horizontal grounding! My tip would be get copper/or in poorer countries galvanized pipe works well enaugh and install it in conjunction with galvanized steel bar/ or do the same but with copper if you can afford it!
@fidelcatsro6948Рік тому
add more earthing rods all around the place the more the better🐱👍🏿
@neilblenkinsop2613Рік тому
All earth rod supplies these days are carbon steel with copper coating add to and go deeper using brass connection.
@yumon65152 роки тому
Sir, can I set the tester 200ohm? Should I take that result? Thank you 🙏
@rictorrictor8882 роки тому
yes..
@GUDANGLAMPUSURYA2 роки тому
Om untuk mengetahui brp kedalaman grounding rod yg di tanam bagaimana ya ? 🙏
@GUDANGLAMPUSURYA2 роки тому
Apakah bisa di test dgn ohm meter tersebut
@rictorrictor8882 роки тому
Kedalam nya sehingga rod gak bisa masuk lagi..baru di uji..jika masih tidak mendapat kan bacaan yg dikehendaki..buat point baru sehingga mendapat bacaan yg paling rendah
@thanhthoangngo25912 роки тому
hi sir, if the screen will perform "1 . " , what's wrong?
@rictorrictor8882 роки тому
show me photo..
@octaviohurtado27792 роки тому
The valor is over the Range selectionated in the istrument or the cables are not conected correctly to the Spikes You should to check again all the conections. If the problem continue changue the Spikes of place.
@thanhthoangngo25912 роки тому
@@octaviohurtado2779 Thank you! I'll check carefully. Good day!
@thanhthoangngo25912 роки тому
@@rictorrictor888 Sorry, I don't know how to share a photo via a youtube comment. Anyway, I'll check my device. Thank you for your guidance.
@MNor-nb8sp2 роки тому
What we do if earth volt not zero
@rictorrictor8882 роки тому
Find another location for grounding the rod..
@30mAkillsРік тому
De-energize that service and procced if the voltage is more than 10.
@FabioHM712 роки тому
the operator wears the helmet because there are suspended loads?
@rictorrictor8882 роки тому
He worries falling mango fruit..hahaha
@FabioHM712 роки тому
@@rictorrictor888 hahahaha ;-)
@fidelcatsro6948Рік тому
there are flying cats around in the neighborhood
@Bwelz2010Рік тому
Good, Thanks
@bruce.bchannel90462 роки тому
Macam mna kalo erathing buat ats tnh bacaan bukit tu tnh...
@rictorrictor8882 роки тому
tetap kena dapat kan bacaan bawah 10 ohm juga...tapi ada kaedah2 untuk menurunkan bacaan jika di buat atas tanah berbukit..tq
@bruce.bchannel90462 роки тому
Sa lbih 15ohm bgtu
@bruce.bchannel90462 роки тому
Nnti whatapps kmi 0138724857 mhu tnya kaedah lain
@rictorrictor8882 роки тому
@@bruce.bchannel9046 boleh tambah point lagi tu..atau guna wayer tembaga bogel gulung jadi kan coil...tanam terus dlm tanah.hujung nya sambung ke electrod yang sedia ada..
@bruce.bchannel90462 роки тому
Mcm mna cara ti
@johnvillellegunas186Рік тому
Hi sir. If floor is concrete, how to insert voltage and currrent spikes?
@fidelcatsro6948Рік тому
break concrete and place into the soil below?
@30mAkillsРік тому
It need not be inserted. Wrap the spikes in wet towel and place them horizontally on the concrete floor with weights (stone) placed on the sack. Wet the whole area by watering.
@fje19487 місяців тому
@@fidelcatsro6948 Jesus, what planet are you on…..
@fje19487 місяців тому
@@30mAkills Excellent explanation….
@fidelcatsro69487 місяців тому
@@fje1948 planet Kittygystan 🐱 of the 23rd Constellation, why do you ask amigo?
@Mike-ry4tiРік тому
Your value of 1.63 ohms is a little high. Ideally less than 1 ohm is what you want...
@lenslens73792 роки тому
I think 1/RT = 1/R1 + 1/R2 + 1/R3
@SpecialVeloce7 місяців тому
Sorry your Appying the wrong formula, it's average, not resistances in paralel
@aruniimalka61232 роки тому
what is this aim?
@rictorrictor8882 роки тому
Protect human and electrical equipment from electric short
@ervingjonaj90823 місяці тому
music is shocking
@johnhayhurst58843 роки тому
Very Very different to how it's done in the UK, In the UK those reading wouldn't be satisfactory but the method is way different so I don't know. Interesting though
@azleeman3 роки тому
Maybe the humidity in UK is different if we compare to Malaysia. The water in soil can effect the meter reading.
@nasrulhelmeihalimppksistem74322 роки тому
@@azleeman biasanya ada 2 jenis earth tester yg selalu diguna measure grounding resistance. yg dlm video ni guna kyoritsu & location potential spike tu ditengah2 antara ground rod & current spike. yg satu lg jenama megger tapi jarak potential spike tu 62% dari jarak antara earth rod & current spike. & potential spike tu kena ubah 10% ke depan % 10% ke belakang dari kedudukan asal & diambil average dr 3 reading td. mungkin kat uk guna jenama megger sbb tu dia ckp different dgn kt sini.
@30mAkillsРік тому
All over the world FOP (Fall of Potential) method is same.
@johnhayhurst5884Рік тому
Incorrect@@30mAkills
@30mAkillsРік тому
@@johnhayhurst5884 then tell the correct. Here our earthing is TT.
@ahmadwahab16413 роки тому
untuk apa select ke earth voltage?
@rictorrictor8883 роки тому
kita uji dahulu jika terdapat voltage dalam tanah.. terutamanya di kawasan kediaman yang berdekatan dengan sub station
@fidelcatsro6948Рік тому
kalau ada voltage baguslah pasang diode boleh charge bateri kereta anda🐱👍🏿
@daspecialist122010 місяців тому
Attack of the silent explanation vid strikes yet again
@rictorrictor88810 місяців тому
Hahaha..Mr bean vers 2
@rjaramilloc10 місяців тому
Ese método no existe, tomaste medidas arbitrarias y sacaste un promedio... No tiene sentido.
@thunderhype59722 роки тому
Sub
@user-vd6wb5ef8v5 місяців тому
Why to use this device with long cables and sticks while THEORETICALLY one can get more relevant results using any household electric appliance like, say, Incandescent light bulb, a mulimeter and the old good Ohm's Law? One terminal of the bulb is connected to live (hot), the other to earth and the current is measured. Divide voltage by current and subtruct the bulb's resistance and the result is the earth resistance. What is wrong in such approach?
@Godfa5394 місяці тому
The results would only be resistance on the load , not main earth resistance
@user-vd6wb5ef8v4 місяці тому
@@Godfa539 will you justify this statement please?
@hidennseek1483Місяць тому
I get what you mean and yes you can get accurate measurement through ohms wall but use a proper load resistor that is large enough to limit the current so the damage you will cause on the ground rod is limited.
@MasudRana-sr1vf2 роки тому
One time check can't ? Why 3 time check,
@rictorrictor8882 роки тому
More accurate ..
@SpecialVeloce7 місяців тому
And if you need to get only one value, measure twice to rule out reading errors.
@johnherbster5110Рік тому
Much too long. Can't stand the music. Should begin with the schematic drawings.
@fje19487 місяців тому
Music is beautiful. If you don’t like the sound, turn the volume down! What an inappropriate comment!