HOW TO PREFORM EARTH RESISTANCE TEST

  Переглядів 229,755

rictor rictor

rictor rictor

3 роки тому

This tutorial show how to carry out earth resistance test for commercial and resident building . Proper setting is importance for getting the better and accurate test result .

КОМЕНТАРІ: 227
@muhdyunus3894
@muhdyunus3894 3 роки тому
Video paling sng difahami...tq sgt2
@MrSyahryzal
@MrSyahryzal 2 роки тому
Mudah untuk difahami... Lama mencari video earthing test untuk menambah ilmu. Terima kasih boss
@kalamsa7445
@kalamsa7445 Рік тому
Without much noise around, explained in a simple practical way...Thanks Rictor
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@castertroycabillar2863
@castertroycabillar2863 2 роки тому
Thanks for this very informative vedio. More power.
@PbaY.
@PbaY. 3 роки тому
mantap tutorial nya .👍👍🌟🌟🌟
@o-techtips3871
@o-techtips3871 2 роки тому
Thank you very much for your sharing very informative tips☺️
@yghiduppastimatikelak8854
@yghiduppastimatikelak8854 2 роки тому
Good job ...thanks for sharing..
@marchomeautorepairs
@marchomeautorepairs 2 роки тому
Keep up the good work
@foonglikwei3913
@foonglikwei3913 2 роки тому
This teaching very useful and very easy to understand. Thanks and appreciate it 😊
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@salumhongo3955
@salumhongo3955 9 місяців тому
You demonstrate this critical task to look easily, Thank you very much a learn a lot through your video.
@fje1948
@fje1948 7 місяців тому
The video I was looking for! Excellent explanation of the test. Thank you so much! Ps: The background music is pleasant and appropriate!
@ohhappyday1548
@ohhappyday1548 2 роки тому
thanks to your efforts, it is very helpful .. thank you..
@manjunathamanju6204
@manjunathamanju6204 3 роки тому
Thank you Sir this video very useful for all Electrical engineers
@kirotomato7316
@kirotomato7316 3 роки тому
easy to understand,thank you sir for wharing the information for us
@ahmedbelazi2318
@ahmedbelazi2318 11 місяців тому
Thank you for the effort made in the video.... I have a question... Is it true that the yellow wire is supposed to be an extension of the red wire, meaning on one line to give the reading... Why change in yellow only and should it be changed in red? ??
@electroboy3607
@electroboy3607 8 місяців тому
Good job..🎉 im practical test
@kanthasamymuthusamy739
@kanthasamymuthusamy739 Рік тому
Simple explainations.Easy to underdstand
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@ofwj-ddah
@ofwj-ddah 10 місяців тому
Thanls for sharingbthis video. It helps me a lots
@MrOner07
@MrOner07 2 роки тому
very easy to follow... you earned a subscriber!❤️😊
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@joselitodupaya2092
@joselitodupaya2092 3 роки тому
Thank you sir sa video
@angelosrcayabyab6952
@angelosrcayabyab6952 2 роки тому
thanks for sharing
@sanjeevraghav3700
@sanjeevraghav3700 Рік тому
Appreciate 👌👌you have done share gr8 experience with kyoritsu instrument 💐 This is sanjeev raghav from kyoritsu
@rictorrictor888
@rictorrictor888 Рік тому
Thank too .kyoritsu always the great equipment ..
@30mAkills
@30mAkills Рік тому
This method is not FOP.
@william5624
@william5624 2 роки тому
Very good👍🏻
@sanjeevraghav3700
@sanjeevraghav3700 Рік тому
Very nice vedio 👌👌kudos to your effort 🙏🙏👌
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@iranweranga225
@iranweranga225 10 місяців тому
Is there a specific number of times that earth resistance testing should be done for a specific area? (like number of times per meter squard)
@akilagayan6533
@akilagayan6533 Рік тому
Good work 👍
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@solomonnyaga7018
@solomonnyaga7018 7 місяців тому
Does it mean now the earth resistance is perfect?
@CrisBoy410
@CrisBoy410 9 місяців тому
video excelente parabens , abraços do Brasil .
@nathan37141
@nathan37141 Рік тому
Thank you Engineer
@gabus1956
@gabus1956 Рік тому
Thank from Hungary
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@fazrulchanneltv9157
@fazrulchanneltv9157 2 роки тому
Tq Sir. Clear and easy to undrstand. This place is like "Bukit Bendera" 😅
@rictorrictor888
@rictorrictor888 2 роки тому
Yes bro..bukit bendera..tqvm
@pankajraina4832
@pankajraina4832 Рік тому
Good sir 👍
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@user-ic5re6so6e
@user-ic5re6so6e 2 роки тому
Thank you, sir
@francisrayang805
@francisrayang805 2 роки тому
Hi sir. You did a very informative video thanks. I've a question for you.In the video you did the test on a big compound. I'm in a terrace house and the compound is very limited. I can't pull the yellow and red cable that long..only 3-4 meters to the nearest soil. Will it affect the reading? Please advice thks.
@rictorrictor888
@rictorrictor888 2 роки тому
In that situation ..You can try nearest area to ground the spike ..
@rictorrictor888
@rictorrictor888 2 роки тому
in that situation ..yes..
@30mAkills
@30mAkills Рік тому
You have to maintain distance. Please read my other comments. Get permission from neighbours.
@jillferrer6135
@jillferrer6135 Рік тому
thank you sir..
@sahayaxaviersahayaxavier3217
@sahayaxaviersahayaxavier3217 3 роки тому
Salute sir
@redbirdgaming7905
@redbirdgaming7905 2 роки тому
Thank you very much sir Many Thanks
@fauzibafana9089
@fauzibafana9089 2 роки тому
Can i know whether before the individual earth rod being tested you have to remove the connection of the earth rod from the rest.
@gniraj8501
@gniraj8501 Рік тому
I am also have same question.
@30mAkills
@30mAkills Рік тому
Yes it should be disconnected from service. If the voltage is more than 10 it will destroy the meter and also give false reading. Please read the user manual reg the max voltage limit that the meter will work safely in energised service without disconnection.
@muhdsolihin2641
@muhdsolihin2641 Рік тому
should be disconnecting earth cable from house to ground chamber first. so you will get the purest ground resistance.
@pankajmishra43
@pankajmishra43 Рік тому
Hiiii... You mean, first disconnect the earth cable from earth pit?? OR Can we shutdown the entire system before measuring earth resistance?? Pls guide
@Sim_Tiby
@Sim_Tiby Рік тому
Disconnect the earth cable.
@DiReal_Donclassy
@DiReal_Donclassy Рік тому
Of course he must have done that before starting the test otherwise the resistances of home equipment will distort the result
@anthondiy
@anthondiy Рік тому
Thank you sir sa video another learning for earthing system
@arturotakuma4742
@arturotakuma4742 Рік тому
excelent ¡¡¡
@fidelcatsro6948
@fidelcatsro6948 Рік тому
if we had no access to such equipment will adding more grounding rods to the ground all connected together potentially reduce the earth resistance?
@rictorrictor888
@rictorrictor888 Рік тому
Yes.
@fidelcatsro6948
@fidelcatsro6948 Рік тому
@@rictorrictor888 🐱👍🏿
@matsetizar65
@matsetizar65 12 днів тому
when lightning strikes the earth doesn't the surge enter the house via the earth wiring? If so isn't it dangerous, probably better not to have any earthing system at all?
@gohpoikheng6030
@gohpoikheng6030 Рік тому
May i know why the cable for current is longer than the voltage?
@raemondbradford1629
@raemondbradford1629 Рік тому
When current is injected into the earth, then the voltage will change around the location of injection. The voltage reference cable spike needs to be some distance from the points where current is injected or removed, in order to try and find a location with minimal disturbance of earth voltage potential.
@wazzer5293
@wazzer5293 5 місяців тому
Sir, how 1). If earth got voltage, what is the next action.. 2). When to use the setting mode 200 & 2000? Apprecite ur answer
@jhunedOz18
@jhunedOz18 Рік тому
Conclusion of 1.62 ohms? Meaning of that value? Is there a range passing value? I'd like to know.
@sanjeevraghav3700
@sanjeevraghav3700 Рік тому
It means your earth grounding is perfect, anything less than 5ohm always consider perfect earthing as per indian standard 🙂
@svh6195
@svh6195 2 роки тому
Thanx!!
@vlogsidah89
@vlogsidah89 3 роки тому
Mantap tuan,done support ya,maaf lewat.. 🙏🙏
@KGL101293
@KGL101293 2 роки тому
Hi, I have a Kyoritsu 4105A unit too, and I am getting "1. . ." reading at 20 ohm dial, who do you think is the problem, and how to fix this? Thank you.
@deutroitcity
@deutroitcity 2 роки тому
It's over limit. U need to dial up the limit. Cannot use 20ohm. Because the reading is above 20 ohm
@nasiadomary4893
@nasiadomary4893 Рік тому
How about if the reading is 25ohms What can i do to get less than 5Ohms?
@30mAkills
@30mAkills Рік тому
@@nasiadomary4893 1. If possible increase the depth of electrode. 2. Insert another electrode at a distance of at least twice the buried depth of 1st electrode and link both at top. Eg.: If 1 st electrode buried depth = 3 M then second electrode should be installed at a distance of minimum 6 M away and both should be linked with wire or strip at the top. 3. Wet the pit by watering because dry earth is a bad conductor. Note : Chemical electrodes are fraud work. Hope all this helps.
@nasiadomary4893
@nasiadomary4893 Рік тому
@@30mAkills Thanks🙏🙏
@siralexivan2006
@siralexivan2006 3 роки тому
well done
@rictorrictor888
@rictorrictor888 3 роки тому
Tqvm
@DaBlackTradesMan
@DaBlackTradesMan Рік тому
I have to perform this same test but outside of the building is all concrete, a shower room will be built in the basement but first the neutral to earth voltage needs to be tested, so how would I go about this?
@frankkennedy7831
@frankkennedy7831 Рік тому
you silly person. what sort of system are you on?
@30mAkills
@30mAkills Рік тому
Check with normal clamp or multimeter in volts mode between earth and neutral of any 3 pin socket connected to that service. The voltage value should be below 2. Hope this helps.
@fje1948
@fje1948 7 місяців тому
@@frankkennedy7831 Perhaps you are the silly person making such an inappropriate comment! 🤢
@prabhus4137
@prabhus4137 2 роки тому
Hi sir I have a doubt. Could you please tell me the difference between 2 point, 3 point method. In megger it has 4 terminals C1, C2, P1, P2. how to measure earth pit resistance?
@30mAkills
@30mAkills Рік тому
Short C1 and P1 and connect to electrode under test. P2 is for potential and C2 is for current spike. This is known as 3 point or Fall of Potential method. 4 terminals method is for testing soil as per Wenner method. This is for civil guys and not for electrical guys. Reg 2 point earth pit resistance testing: In India we don't/cant use this method because our public water supply is thru PVC pipes which is non conductor. Hope this helps.
@leomarbecilla2785
@leomarbecilla2785 Рік тому
hi sir. how do you perform it in a building where there is no earth ground to put the spike?
@rictorrictor888
@rictorrictor888 Рік тому
Extent green wire..
@rictorrictor888
@rictorrictor888 Рік тому
For condo there should have main electrical grounding
@dakwahislamcn6390
@dakwahislamcn6390 3 роки тому
Lanjutkan
@bornstar9897
@bornstar9897 2 роки тому
thanks
@anthonykihanga2881
@anthonykihanga2881 Рік тому
Thanks alot
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@bundaajhalah
@bundaajhalah 3 роки тому
Hadir nyimak 👍
@rictorrictor888
@rictorrictor888 3 роки тому
thank you so much
@neilblenkinsop2613
@neilblenkinsop2613 Рік тому
To individually test the earth rod disconnect tape from earth rod
@surendrakverma555
@surendrakverma555 Рік тому
Good 🙏🙏🙏🙏🙏
@30mAkills
@30mAkills Рік тому
Shifting potential spike towards right and left is wrong.
@dumindathusuth2026
@dumindathusuth2026 Рік тому
@castertroycabillar2863
@castertroycabillar2863 2 роки тому
Sir what is the porpuse for higher ohms setting.is it same result as 20ohms setting.thanks
@rictorrictor888
@rictorrictor888 2 роки тому
Yes..same.
@30mAkills
@30mAkills Рік тому
For soil testing and also in hill areas.
@igorsmirnoff8578
@igorsmirnoff8578 Рік тому
Будьте любезны,выложите такое же видео с прибором KEW 4106,спасибо!!!
@niezam1729
@niezam1729 2 роки тому
Jika persekitaran rumah tamn agak sukar nk ambil bacaan,sb permukaan tanah @ berturap simen Dan jalan tar. 1- minutes 6.15 mase kita clamp wayar di electrod bumi.yg seeloknya copper tape @ cable incoming perlu ditanggalkan @ tidak semasa nak ambil bacaan.klu sye lihat Tuan x buka ..
@nasrulhelmeihalimppksistem7432
@nasrulhelmeihalimppksistem7432 2 роки тому
kalau kawasan tar @ bersimen, boleh guna metal screen @ earthing mat. letak pada jarak yg ditetapkan & siram dgn air jd blh buat measurement
@japhethm6103
@japhethm6103 3 місяці тому
What readings should tell me that the resistance is not okay please
@rictorrictor888
@rictorrictor888 3 місяці тому
depend on local regulation ..as lower as possible. .below 10ohm
@azleeman
@azleeman 3 роки тому
Saya nak tanya, bukankah testing dibuat semasa pemasangan rod sahaja (sebelum kita sambungkan dengan earth DB atau sebelum sambung ke perlindungan kilat)
@rictorrictor888
@rictorrictor888 3 роки тому
Kedua2 nya boleh ..sebelum dan selepas ..Sebenarnya Cooper tape itu bukan utk pelindung kilat..
@yosuaabimo9379
@yosuaabimo9379 4 місяці тому
Test ini apakah harus saat listrik off?
@stanleyozoilo1587
@stanleyozoilo1587 Рік тому
What is the accurate value for best low resistance using Megger machine
@rictorrictor888
@rictorrictor888 Рік тому
0 ohm
@30mAkills
@30mAkills Рік тому
@@rictorrictor888 Practically not possible. Is earth full of gold?
@fje1948
@fje1948 7 місяців тому
@@rictorrictor888 I wish 😂
@wtnyambizi9876
@wtnyambizi9876 Рік тому
What about the distance btn the spikes does it matter !?
@anthonykihanga2881
@anthonykihanga2881 Рік тому
5 meters up to 10 meters it depends on soil type
@30mAkills
@30mAkills Рік тому
Thumb rule for current spike distance from electrode = Minimum 8 to 10 times the buried depth of earth electrode. Eg., If earth electrode is 3 M long then C spike should placed about 24 to 30 M distance. This is to avoid '"zone of influence"' factor. Most manufacturers wont tell this because the distance will affect their tester sales in city and town areas where space is congested. So they suggest 5 M and 10 M which will not yield correct value. I challenge Kyoritsu in this matter.
@fje1948
@fje1948 7 місяців тому
@@30mAkills Thank you for this comment - can you please provide some formal references to confirm y you our comment - Thank you!
@lonedragon4410
@lonedragon4410 2 роки тому
Below 5ohm is acceptable right?
@rictorrictor888
@rictorrictor888 2 роки тому
Yes
@wilsonloo8576
@wilsonloo8576 3 роки тому
Hi Rictor , may i know how to know the result is good or bad? Many Thanks
@rictorrictor888
@rictorrictor888 3 роки тому
low in reading is the batter .must below 10ohm.some time we can get 0 ohm. that the best..
@octaviohurtado2779
@octaviohurtado2779 2 роки тому
It depends on your country standards. But the Best is the nearest to 0 ohms which is imposible to get 0 ohms. Also there are many methods to make the measurraments, it depends on your country standards too.
@loveandpeace594
@loveandpeace594 Рік тому
thanks :)
@30mAkills
@30mAkills Рік тому
Shifting potential spike in perpendicular ( left and right)direction is not correct.
@aruquest25
@aruquest25 3 роки тому
The green wire is for?
@rictorrictor888
@rictorrictor888 3 роки тому
electrode wire..
@olegkotletov7857
@olegkotletov7857 3 роки тому
green wire is for grass. grass is green. make sense right? put green wire on grass and see resistance of grass. grass is green, green wire is green too. make sense right? right.
@ericmunkanta2964
@ericmunkanta2964 26 днів тому
Why is the leads in the same line
@Bestofthebest383
@Bestofthebest383 7 днів тому
I had an exams question in college how to do earth rod test . I didn’t pass it 😢
@islammaidul6999
@islammaidul6999 Рік тому
Overall resistance how is it calculation sir
@rictorrictor888
@rictorrictor888 Рік тому
Total of test 1 ,2 ,3 then / by 3..it show on video min 13.20
@muhammadaresyamilbinazman7935
@muhammadaresyamilbinazman7935 Рік тому
Tumpang tanya, kan ada 20ohm, 200ohm, dan 2000ohm. Yang tu nak laraskan berdasarkan faktor apa ye?
@fidelcatsro6948
@fidelcatsro6948 Рік тому
dasarkan 20ohm setting
@AutodidactEngineer
@AutodidactEngineer Рік тому
The test should be done preferably during the driest season to prevent moisture from ruinning your values!
@File-Transfer
@File-Transfer Місяць тому
I have a question, engr. Why is it required in the earth resistance tester manual to damp the surroundings?
@AutodidactEngineer
@AutodidactEngineer Місяць тому
@@File-Transfer I don't know about that
@junsmackalbos4565
@junsmackalbos4565 10 місяців тому
Sir the result you shown is that good or bad grounding
@rictorrictor888
@rictorrictor888 10 місяців тому
Good ..under 10 ohm
@junsmackalbos4565
@junsmackalbos4565 10 місяців тому
Thanks sir......
@yusufsupyan9940
@yusufsupyan9940 3 роки тому
Luar biasa kawan Videonya. Sudah saya kirim Bungkusan komplit dan,paten, durasipun Aman. Sesuai undangan. Ditunggu Amanahnya ya..
@rictorrictor888
@rictorrictor888 3 роки тому
Ya udah juga..terima kasih..
@kennedymutuku8950
@kennedymutuku8950 Рік тому
Hello Sir,what if the result is above 10,let say 50..how can you improve this to 5?
@AutodidactEngineer
@AutodidactEngineer Рік тому
Use a combination of vertical and horizontal grounding! My tip would be get copper/or in poorer countries galvanized pipe works well enaugh and install it in conjunction with galvanized steel bar/ or do the same but with copper if you can afford it!
@fidelcatsro6948
@fidelcatsro6948 Рік тому
add more earthing rods all around the place the more the better🐱👍🏿
@neilblenkinsop2613
@neilblenkinsop2613 Рік тому
All earth rod supplies these days are carbon steel with copper coating add to and go deeper using brass connection.
@yumon6515
@yumon6515 2 роки тому
Sir, can I set the tester 200ohm? Should I take that result? Thank you 🙏
@rictorrictor888
@rictorrictor888 2 роки тому
yes..
@GUDANGLAMPUSURYA
@GUDANGLAMPUSURYA 2 роки тому
Om untuk mengetahui brp kedalaman grounding rod yg di tanam bagaimana ya ? 🙏
@GUDANGLAMPUSURYA
@GUDANGLAMPUSURYA 2 роки тому
Apakah bisa di test dgn ohm meter tersebut
@rictorrictor888
@rictorrictor888 2 роки тому
Kedalam nya sehingga rod gak bisa masuk lagi..baru di uji..jika masih tidak mendapat kan bacaan yg dikehendaki..buat point baru sehingga mendapat bacaan yg paling rendah
@thanhthoangngo2591
@thanhthoangngo2591 2 роки тому
hi sir, if the screen will perform "1 . " , what's wrong?
@rictorrictor888
@rictorrictor888 2 роки тому
show me photo..
@octaviohurtado2779
@octaviohurtado2779 2 роки тому
The valor is over the Range selectionated in the istrument or the cables are not conected correctly to the Spikes You should to check again all the conections. If the problem continue changue the Spikes of place.
@thanhthoangngo2591
@thanhthoangngo2591 2 роки тому
@@octaviohurtado2779 Thank you! I'll check carefully. Good day!
@thanhthoangngo2591
@thanhthoangngo2591 2 роки тому
@@rictorrictor888 Sorry, I don't know how to share a photo via a youtube comment. Anyway, I'll check my device. Thank you for your guidance.
@MNor-nb8sp
@MNor-nb8sp 2 роки тому
What we do if earth volt not zero
@rictorrictor888
@rictorrictor888 2 роки тому
Find another location for grounding the rod..
@30mAkills
@30mAkills Рік тому
De-energize that service and procced if the voltage is more than 10.
@FabioHM71
@FabioHM71 2 роки тому
the operator wears the helmet because there are suspended loads?
@rictorrictor888
@rictorrictor888 2 роки тому
He worries falling mango fruit..hahaha
@FabioHM71
@FabioHM71 2 роки тому
@@rictorrictor888 hahahaha ;-)
@fidelcatsro6948
@fidelcatsro6948 Рік тому
there are flying cats around in the neighborhood
@Bwelz2010
@Bwelz2010 Рік тому
Good, Thanks
@bruce.bchannel9046
@bruce.bchannel9046 2 роки тому
Macam mna kalo erathing buat ats tnh bacaan bukit tu tnh...
@rictorrictor888
@rictorrictor888 2 роки тому
tetap kena dapat kan bacaan bawah 10 ohm juga...tapi ada kaedah2 untuk menurunkan bacaan jika di buat atas tanah berbukit..tq
@bruce.bchannel9046
@bruce.bchannel9046 2 роки тому
Sa lbih 15ohm bgtu
@bruce.bchannel9046
@bruce.bchannel9046 2 роки тому
Nnti whatapps kmi 0138724857 mhu tnya kaedah lain
@rictorrictor888
@rictorrictor888 2 роки тому
@@bruce.bchannel9046 boleh tambah point lagi tu..atau guna wayer tembaga bogel gulung jadi kan coil...tanam terus dlm tanah.hujung nya sambung ke electrod yang sedia ada..
@bruce.bchannel9046
@bruce.bchannel9046 2 роки тому
Mcm mna cara ti
@johnvillellegunas186
@johnvillellegunas186 Рік тому
Hi sir. If floor is concrete, how to insert voltage and currrent spikes?
@fidelcatsro6948
@fidelcatsro6948 Рік тому
break concrete and place into the soil below?
@30mAkills
@30mAkills Рік тому
It need not be inserted. Wrap the spikes in wet towel and place them horizontally on the concrete floor with weights (stone) placed on the sack. Wet the whole area by watering.
@fje1948
@fje1948 7 місяців тому
@@fidelcatsro6948 Jesus, what planet are you on…..
@fje1948
@fje1948 7 місяців тому
@@30mAkills Excellent explanation….
@fidelcatsro6948
@fidelcatsro6948 7 місяців тому
@@fje1948 planet Kittygystan 🐱 of the 23rd Constellation, why do you ask amigo?
@Mike-ry4ti
@Mike-ry4ti Рік тому
Your value of 1.63 ohms is a little high. Ideally less than 1 ohm is what you want...
@lenslens7379
@lenslens7379 2 роки тому
I think 1/RT = 1/R1 + 1/R2 + 1/R3
@SpecialVeloce
@SpecialVeloce 7 місяців тому
Sorry your Appying the wrong formula, it's average, not resistances in paralel
@aruniimalka6123
@aruniimalka6123 2 роки тому
what is this aim?
@rictorrictor888
@rictorrictor888 2 роки тому
Protect human and electrical equipment from electric short
@ervingjonaj9082
@ervingjonaj9082 3 місяці тому
music is shocking
@johnhayhurst5884
@johnhayhurst5884 3 роки тому
Very Very different to how it's done in the UK, In the UK those reading wouldn't be satisfactory but the method is way different so I don't know. Interesting though
@azleeman
@azleeman 3 роки тому
Maybe the humidity in UK is different if we compare to Malaysia. The water in soil can effect the meter reading.
@nasrulhelmeihalimppksistem7432
@nasrulhelmeihalimppksistem7432 2 роки тому
@@azleeman biasanya ada 2 jenis earth tester yg selalu diguna measure grounding resistance. yg dlm video ni guna kyoritsu & location potential spike tu ditengah2 antara ground rod & current spike. yg satu lg jenama megger tapi jarak potential spike tu 62% dari jarak antara earth rod & current spike. & potential spike tu kena ubah 10% ke depan % 10% ke belakang dari kedudukan asal & diambil average dr 3 reading td. mungkin kat uk guna jenama megger sbb tu dia ckp different dgn kt sini.
@30mAkills
@30mAkills Рік тому
All over the world FOP (Fall of Potential) method is same.
@johnhayhurst5884
@johnhayhurst5884 Рік тому
Incorrect@@30mAkills
@30mAkills
@30mAkills Рік тому
@@johnhayhurst5884 then tell the correct. Here our earthing is TT.
@ahmadwahab1641
@ahmadwahab1641 3 роки тому
untuk apa select ke earth voltage?
@rictorrictor888
@rictorrictor888 3 роки тому
kita uji dahulu jika terdapat voltage dalam tanah.. terutamanya di kawasan kediaman yang berdekatan dengan sub station
@fidelcatsro6948
@fidelcatsro6948 Рік тому
kalau ada voltage baguslah pasang diode boleh charge bateri kereta anda🐱👍🏿
@daspecialist1220
@daspecialist1220 10 місяців тому
Attack of the silent explanation vid strikes yet again
@rictorrictor888
@rictorrictor888 10 місяців тому
Hahaha..Mr bean vers 2
@rjaramilloc
@rjaramilloc 10 місяців тому
Ese método no existe, tomaste medidas arbitrarias y sacaste un promedio... No tiene sentido.
@thunderhype5972
@thunderhype5972 2 роки тому
Sub
@user-vd6wb5ef8v
@user-vd6wb5ef8v 5 місяців тому
Why to use this device with long cables and sticks while THEORETICALLY one can get more relevant results using any household electric appliance like, say, Incandescent light bulb, a mulimeter and the old good Ohm's Law? One terminal of the bulb is connected to live (hot), the other to earth and the current is measured. Divide voltage by current and subtruct the bulb's resistance and the result is the earth resistance. What is wrong in such approach?
@Godfa539
@Godfa539 4 місяці тому
The results would only be resistance on the load , not main earth resistance
@user-vd6wb5ef8v
@user-vd6wb5ef8v 4 місяці тому
@@Godfa539 will you justify this statement please?
@hidennseek1483
@hidennseek1483 Місяць тому
I get what you mean and yes you can get accurate measurement through ohms wall but use a proper load resistor that is large enough to limit the current so the damage you will cause on the ground rod is limited.
@MasudRana-sr1vf
@MasudRana-sr1vf 2 роки тому
One time check can't ? Why 3 time check,
@rictorrictor888
@rictorrictor888 2 роки тому
More accurate ..
@SpecialVeloce
@SpecialVeloce 7 місяців тому
And if you need to get only one value, measure twice to rule out reading errors.
@johnherbster5110
@johnherbster5110 Рік тому
Much too long. Can't stand the music. Should begin with the schematic drawings.
@fje1948
@fje1948 7 місяців тому
Music is beautiful. If you don’t like the sound, turn the volume down! What an inappropriate comment!
Earth Electrode Testing
14:16
John Ward
Переглядів 492 тис.
didn't want to let me in #tiktok
00:20
Анастасия Тарасова
Переглядів 8 млн
CONTROLA O TEU AR CONDICIONADO!
10:02
A Minha Casa Digital
Переглядів 165
INSTALLING AN EARTH ELECTRODE
7:36
Bristolsparky
Переглядів 3,5 тис.
Earthing vs. grounding
7:06
Paul Saladino MD
Переглядів 63 тис.
Earth loop impedance test, ZE test
4:56
Universal Skills
Переглядів 58 тис.
Ground Resistance Measurement, Fall potential method
4:01
JVASecurity
Переглядів 231 тис.
Why The Clamp Meter Is The Only Tester You Need | Pros and DIYers
8:12
Everyday Home Repairs
Переглядів 523 тис.
How to do earth electrode resistance test/ and reduce resistance to earth
8:58