7 EICR FAILS - Inspection and Testing DEEP DIVE

  Переглядів 63,677

Artisan Electrics

Artisan Electrics

День тому

In this video we go in depth on some of the reasons a house could fail it's EICR inspection with information for homeowners, apprentices and experienced electricians too.
Tradify - bit.ly/3HE3PGy
Links to all the tools used in the EICR:👇
Fluke Voltalert: amzn.to/4byxzSN
Megger MFT 1741+ Multi Function Tester: amzn.to/3HYUusX
R2 Long Wander Lead: amzn.to/42Fr9gG
Boddingtons Inspection Mirror: amzn.to/3SXJPnB
Kewtech Jump Leads: amzn.to/3HVRvRQ
Boddingtons Insulated Screwdrivers: amzn.to/3OGeXq6
Knives Long Nose Pliers: amzn.to/3OGJa8E
Bosch Electric Screwdriver: amzn.to/3unxoJv
Unilite IL925R: unilite.co.uk/product/il-925r/
Unilite Head Torch: unilite.co.uk/product/hl-11r/
TIS Earth Leakage Clamp Meter: bit.ly/49yxFrH
Unilite Knife: unilite.co.uk/product/fk3/
Jackery Power Bank: uk.jackery.com?aff=142
Kewtech Plug In Tester: amzn.to/49BrGmb
🚨Subscribe to our UKposts Channel for more great electrical content: ukposts.info...
➕Get more from Artisan Electrics here!👇
linktr.ee/artisanelectrics
Get a quote from us here: forms.openquote.net/company/a...
🔋Use my referral link to purchase a Tesla product and get free credits you can redeem for awards like Supercharging miles, merchandise and accessories.
ts.la/andrew24855
💬Artisan Electric Discord - Join our Electrical Community! 👇
/ discord
🔔 Become a Channel Member To Get Access To Exclusive Perks 👇
➤ / @artisanelectrics
🔔 Subscribe to TOOLS4SPARKS UKposts Channel 👇
We Also Have A Dedicated UKposts Channel About Tools:
➤ / tools4sparks
⏱️Timestamps
00:00 - Introduction
00:30 - Step 1 - Talk to the customer
01:37 - What is an EICR?
04:25 - Visual Inspection process
09:30 - 1st reason why your house will fail an EICR
13:35 - This could be a concern…
16:17 - What do the codes mean?
17:52 - Starting the test sequence
22:06 - Special message from Tradify
24:16 - 2nd reason why your house will fail an EICR
25:18 - Let me explain
28:10 - R1 and R2 testing
30:14 - Calculating cable resistance
32:44 - 3rd reason why your house will fail an EICR
37:51 - What on earth happened here?
39:40 - Looking at the smoke detectors
40:57 - 4th reason why your house will fail an EICR
42:25 - Adventuring into the loft
47:22 - Ring continuity test
49:02 - 5th reason why your house will fail an EICR
49:56 - How to do the figure of eight test
52:50 - 6th reason why your house will fail an EICR
54:15 - If you are a customer, please don’t use these!
56:52 - Insulation resistance test
59:05 - series of Impedance tests
1:01:35 - RCD testing
1:03:00 - Do this after you have finished testing
PARTNERS/ARTISAN CODES
🔦Unilite Work Lights: Get 25% off all Unilite Products using our code "ARTISAN25"
UK Store - bit.ly/UNILITE
Europe Store - bit.ly/UNILITE-EU
USA Store - bit.ly/UNILITE-NA
Australia Store - bit.ly/UNILITE-AUS
💪🏼Powered by Hilti Nuron - hilti.to/nuron_range
💳American Express Business Gold Card
Sign up for an AE Business Gold Card using the following link to get a bulk of FREE membership rewards points - bit.ly/3JDmXVG
🥾 Big Boots - Save 10% on our amazing work boots when you use our discount code "ARTISAN10" at checkout here bit.ly/BIGBOOTS
📚 Get 10% off when you use our discount code "Artisan" at checkout Here - bit.ly/3uY94dW-StudyStickers
🔋 Save 5% on EcoFlow Products using code 'AE5' - dada.link/58lAne
🎵 Use music the Artisan Way - Sign up to Epicmedic Sound here 👇🏼
www.epidemicsound.com/referra...
TRADES INSURANCE DISCOUNT
🦏 Use Discount Code “ART5” and you get a 5% Extra Discount On Their Already Excellent Prices.
➤ www.rhinotradeinsurance.com/quote 📞 or call 01162437904.
ENERGY PROVIDER
🐙 Get £50 credit when you switch to Octopus Energy 👇
➤ share.octopus.energy/zappy-sh...
📈Make the most of your UKposts analytics with TubeBuddy - Sign up here👇
➤www.tubebuddy.com/ARTISAN
AMAZON LINKS
✅ Check Out All Our Favourite Tools Here 👇
➤ www.amazon.co.uk/shop/artisan...
🏷️ DISCOUNT BUSINESS SUPPLIES 👇
➤ www.amazon.co.uk/tryAB?tag=ar...
📱 ARTISAN SOCIALS 📱
💬 Artisan Electrics Discord
➤ / discord
📸 Artisan Electrics Instagram Account 👇
➤ / artisanelectrics
📓 Artisan Electrics Facebook Account 👇
➤ / artisanelectrics
⏰ Artisan Electrics TikTok Account
➤ / artisanelectrics
🎥 Get in touch with the Media Team
➤media@artisanelectrics.co.uk
This video is for entertainment purposes only please do not attempt to copy or recreate it. Do so at your own risk.
#sparkylife #electricianlife #artisanelectrics

КОМЕНТАРІ: 373
@artisanelectrics
@artisanelectrics 3 місяці тому
If you would like an EICR then make sure to get in touch with us following the link here 👉 Get a quote from us here: forms.openquote.net/company/artisanelectrics
@CommercialGasEngineerVideos
@CommercialGasEngineerVideos 2 місяці тому
Nice one
@BrianG61UK
@BrianG61UK 2 місяці тому
Jackery Power Bank link seems wrong. It's asking me to log in to the affiliate program.
@artisanelectrics
@artisanelectrics 2 місяці тому
uk.jackery.com?aff=142 - This link should work, apologies there!
@williammartinculleton5875
@williammartinculleton5875 2 місяці тому
Excellent promotional video Sir, Ive always said “ the future is sales “ sadly no Female electrician as yet in the team.
@7KIslands
@7KIslands 2 місяці тому
@@artisanelectrics Great videos . can i ask ? does having only one double plug socket per room and 3 double sockets in the kitchen fail a EICR Thanks .
@halesworth01
@halesworth01 2 місяці тому
Nice to have you back 'on the tools' also nice to have full 'in depth' stuff, I'm not a sparky, but its very interesting!
@artisanelectrics
@artisanelectrics 2 місяці тому
Glad you enjoyed it!
@cjmillsnun
@cjmillsnun 2 місяці тому
That plug to the single socket to the tumble dryer is no code observation. The reason being is it is run from a plugtop and is therefore not fixed wiring. No RCD to lights in the bathroom would not be a fail, it's a C3, as it was allowable at the time of installation. Obviously a recommendation is to upgrade to RCD protection.
@johnwarwick4105
@johnwarwick4105 2 місяці тому
Agreed
@tobysherring1369
@tobysherring1369 2 місяці тому
​@@johnwarwick4105agreed, but it is acceptable to comment on wiring connected via a plug. It is not a Code issue but it would be a responsible thing to do. In this case it's not obviously dangerous (though is the outer sheath of the T&E fully under the cord grip?), but take the case of an elderly, blind or otherwise vulnerable person who has a EICR and they use an old fan heater, kettle, tumble dryer, etc with a damaged flex, or a class 1 flouro batten in a garage, connected via a plug, but with no earth and hanging on rusty nails. Or an extension lead out of a window to a shed, with semi-permanent fixings. These things are very common and potentially lethal, but not part of the EICR. I would note them, at the very least, and may suggest a PAT at little or no cost.
@cjmillsnun
@cjmillsnun 2 місяці тому
@@tobysherring1369 As I said, a no code observation - ie a comment.
@swifty5783
@swifty5783 2 місяці тому
Agreed - providing there is supplementary bonding present to the correct standard.
@callumsimpson7483
@callumsimpson7483 2 місяці тому
The bathroom would be a c2 if it wasn’t protected by rcd and within a special location
@corymac
@corymac 2 місяці тому
Nice work! 🙌🏽
@artisanelectrics
@artisanelectrics 2 місяці тому
Thank you 🙌
@tobysherring1369
@tobysherring1369 2 місяці тому
A shaver socket isn't SELV! It's 230v and (often) 110v. It's permitted not because it's SELV, but because it's transformer isolated and current limited to about 20VA. You really should know better...as you're offering this as training for other electricians.
@andywindy
@andywindy 2 місяці тому
Should it not be 600mm from the Basin as well?
@gdexterc
@gdexterc 2 місяці тому
No @@andywindy
@zjzozn
@zjzozn 21 день тому
Yeah cos the shaver lead won’t reach to see the mirror over the sink 😊
@cumberland1234
@cumberland1234 2 місяці тому
Good educational video, I’d re-do the gas bond clamp as the tag shouldn’t be in contact with the pipe
@artisanelectrics
@artisanelectrics 2 місяці тому
Good tip!
@alvina69
@alvina69 2 місяці тому
Just a couple of things… 1. The main protective bond connection should be made before any branches pipe work and within 600mm of the gas meter, so having it just after the elbow is fine. 2. The vertical height in locations containing a bath or shower is 2.25m not 2.2m. 3. The R1+R2 test should be linked at the board with the CPC of the circuit you’re testing disconnected from the earth bar as leaving it connected will introduce parallel paths.
@Spark101.
@Spark101. 2 місяці тому
There are more than a couple of things……he wouldn’t get half as much stick if he didn’t look down his nose at a standard sparky! Constantly saying ‘ we do it the artisan way’ like they are a special breed! I would say they are bog standard.
@MrMax247
@MrMax247 2 місяці тому
I think that might be tongue and cheek humour 😂, I don't think he ever claimed to be the best or know everything. He certainly puts his reputation on the line just by posting his videos and getting stick from people. Fair play to him 😊
@Spark101.
@Spark101. 2 місяці тому
@@MrMax247 tongue in cheek? He has 5 star electricians embroidered on the back of his t shirts 😂
@thequietroom3991
@thequietroom3991 2 місяці тому
Good job correcting that zone height, that 50mm difference could save someone's life.
@alvina69
@alvina69 2 місяці тому
@@thequietroom3991 Or it might help someone pass their exam.
@franklinodom4259
@franklinodom4259 2 місяці тому
As a tech in another field, i deal with the result of earth faults, and have always been stumped as to what could cause it. Obviously not my job to determine that, just to determine thats whats causing our equipment failure. But many customers dont take my word to contact an electrician to remedy it. And we are back out multiple times, sometimes with noticeable arcing and thermal damage to adj wood and metal fixtures. Super sketchy. Seeing your info on earth leakage, and appliances backfeeding voltage clues me into things ive previously thought were issues. Its always old houses with no earth protection on any outlets except kitchen/bathroom (pre 1960s here?). What a pain. Thanks for the info!
@dugandav1
@dugandav1 2 місяці тому
Great video, noted your comments on the rain circuit. May I suggest you do a video on this and answer the following questions, what would you replace the ring circuit with what are the advantages and disadvantages of a ring circuit? What do they do in Europe instead of a ring circuitETC. I look forward to seeing a new video from you on this subject. Thank you for your content.
@imark7777777
@imark7777777 2 місяці тому
Nice video. Some of the tips between homeowner and electrician were not very well indicated but it I think it did a very good job of going over everything that's involved.
@scott4shell
@scott4shell 2 місяці тому
You have to disconnect the gas bond both ends if they are not identified in the board, gas pipe is metal all the way to the boiler and if you water pipe is metal all the way they will read through on the boiler plate
@skfalpink123
@skfalpink123 2 місяці тому
Many thanks for an excellent and instructive video
@ForTheBirbs
@ForTheBirbs 2 місяці тому
Good one Jordan and Luke
@scott4shell
@scott4shell 2 місяці тому
The smoke alarms have nothing to do with the EICR if they are out of date it’s just a note
@KevinOsborne1987
@KevinOsborne1987 2 місяці тому
The mains aspect needs checking. 90% of the time those smokes have singles into choc blocks loose in the ceiling!
@Lewdacris916
@Lewdacris916 2 місяці тому
If they are fed by grid power then they are part of the house system and should be checked
@Joanddave
@Joanddave 2 місяці тому
No joke my friend. The electrician performing the EICR has a duty of care to fail the smoke detector as it poses a danger to the occupants. Same for any appliance they find faulty. They have to make safe.
@scott4shell
@scott4shell 2 місяці тому
Cheers for the advice I only say this because I noted that there was no smokes present on a EICR and the NIC EIC inspector said that’s not part of the test?
@Joanddave
@Joanddave 2 місяці тому
Yeah l know what you are saying but l couldn't live with myself if they had a fire resulting in a death
@shiamjad
@shiamjad 2 місяці тому
Very helpful video Indeed...
@EMEL-hr4ut
@EMEL-hr4ut 15 днів тому
Artsian are warriors bringing great up-to-date content. If i had the money and lived in Cambridgeshire, i would definitely use you! 😅
@kiandymundi
@kiandymundi 2 місяці тому
Around 18 mins in you explain how doing the dead and live tests in order is a faff But, doesn't each test rely on the previous to be valid? Isn't the order of the tests essential to the overall testing? I was taught to do my continuities way before Ze's
@Mainly_Electrical
@Mainly_Electrical 2 місяці тому
Yes it's important.. dead tests then live tests .. people who haven't got a clue what they're doing will think is brilliant stuff
@chimpalahee
@chimpalahee 2 місяці тому
Great video!
@rowanhoggarth4329
@rowanhoggarth4329 2 місяці тому
Around 12min you said the shaver socket was SELV, but probably meant SLV. Nice video as always, keep up the good work!
@davewellsheatingengineer
@davewellsheatingengineer 2 місяці тому
Great video, I am a gas engineer, our regs insist that there is an earth to the gas supply, however I have noticed that these are now often not fitted due to the gas supply coming to meter is in plastic.. so we seem to have a discrepancy between your regs and ours. Could you clarify please, it would be helpful for us plumbers 😊
@Joanddave
@Joanddave 2 місяці тому
Jordan did say that it is not required, but l would as the customer may extend the water supply to an outside tap using copper pipe
@johnsparkz4728
@johnsparkz4728 Місяць тому
see gas regs 18-1-2
@kevanswift7797
@kevanswift7797 2 місяці тому
Blue-Tack pulls out those very nice screw covers on the sockets, very easy, makes socket look alot better. Noticed metal back box not bonded to socket.
@cjmillsnun
@cjmillsnun 2 місяці тому
Metal back box is bonded by the screws into the socket. The socket will have an earth strap that runs between the screw holes and the earth connection.
@kevanswift7797
@kevanswift7797 2 місяці тому
And when the socket is pulled forward for inspection, the back box is not now earthed and is at its most dangerous position as the cable could come into contact with back box and become live. Do the job properly.
@dannyroberts8822
@dannyroberts8822 2 місяці тому
Bonding the back box isn't required, the socket should be dead before you unscrew it
@alexkay1270
@alexkay1270 2 місяці тому
As long as one lug is of the fixed / static type, there is no requirement to link the cpc to the back box.
@kevanswift7797
@kevanswift7797 2 місяці тому
@@alexkay1270 so when socket is pulled forward (both screws removed) there is no earth on metal back box. Read your regs book and understand. What harm is there in linking. Oh takes longer.
@thetruth6693
@thetruth6693 2 місяці тому
No rcd protection for the bathroom is a fail? I thought that would be a C3 because it was installed to regs at the time
@dangraves7808
@dangraves7808 2 місяці тому
It is a c3 the eicr is not retrospective and as you say it was compliant at the time of installation
@pauldavies9709
@pauldavies9709 2 місяці тому
There's a bit more to the story. If the bathroom has the original supplementary bonding installed on the pipework it's a C3. 99% of the time the supplementary bonding will have been removed during the first bathroom upgrade and leaves you without the compliance to the regulations at the time hence C2.
@alexkay1270
@alexkay1270 2 місяці тому
OK if supplementary bonding
@jamieisbadiof6106
@jamieisbadiof6106 2 місяці тому
finally, a long video I can BING WATCH !!!!!!!! KEEP THIS UP
@paddyaaron82
@paddyaaron82 Місяць тому
Is there any difference between an earth leakage amp meter and a standard amp meter is it possible to check earth leakage on tails with standard amp meter?. Can't seem to find anything online to answer that?
@EMEL-hr4ut
@EMEL-hr4ut 15 днів тому
That loft. I would want crawl boards to go over that. Wouldn't fancy a circus act 😅
@geraldelwood9660
@geraldelwood9660 2 місяці тому
Is it part of the Regs that we are not allowed to calculate R1+R2 by deducting Zs DB from Zs at end of line ?
@mohamedsiadabdille7631
@mohamedsiadabdille7631 2 місяці тому
well done and appreciate tips EICR thanks
@artisanelectrics
@artisanelectrics 2 місяці тому
Glad you like them!
@waithereivegonetogethelp3240
@waithereivegonetogethelp3240 2 місяці тому
33:22 way to avoid committing! What do YOU call that? C2 or C3? personally, C2 (potentially dangerous) is when there's a real danger of damage to the exposed single insulated cable.. is that likely inside the ceiling? I leave that for you to debate in the comments !
@ejharrison3856
@ejharrison3856 2 місяці тому
Hi there, this might be me not under standing. But was/is there a new Reg on testing RCD/RCBO. (50% 100% ect). I thought I read something about it decreasing the life of them
@James-yb6kj
@James-yb6kj Місяць тому
Isnt the cooker isolator and another plug on the other side too close to the gas hob? I thought there was supposed to be a 6cm horizontal gap going vertically from the edges of the hob?
@Ragnar8504
@Ragnar8504 2 місяці тому
A couple of obersvations. 1) I think it's "Safety Extra Low Voltage" (as opposed to FELV, Functional Extra Low Voltage). 2) If the cables inside the immersion cupboard are flexes with appropriate strain relief at both ends I don't really see why they'd need to be fixed. 3) I'd agree with the C3 on the tumble dryer connection, I can't imagine you're supposed to wire T&E into a plug. Even running an extension lead through a hole in the work top would have been a better solution but I'd probably have run a quality extension lead right to the dryer, above the work top. In an ideal world you'd obviously run a spur to a socket under the sink, fused or unfused depending on the details of the circuit.
@tobysherring1369
@tobysherring1369 2 місяці тому
A shaver socket however is not SELV. It's mains voltage, but transformer isolated and limited to 20 watts or so.
@Ragnar8504
@Ragnar8504 2 місяці тому
@@tobysherring1369 Yes, it's just a 1:1 isolation transformer.
@cjmillsnun
@cjmillsnun 2 місяці тому
The tumble dryer connection because it's on a plug is not fixed wiring and not covered by an EICR. I would certainly add a note, but it isn't a code.
@ionskies
@ionskies 2 місяці тому
8.27 mins into vid water bonding I thought the bondings were there to earth metal pipe works within the building irrespective of a pvc water/ gas main supply?
@tobysherring1369
@tobysherring1369 2 місяці тому
What is not right and not safe about the attic lights wiring? I know it's hardly standard, but what's unsafe, exactly?
@IAAITKEN
@IAAITKEN 2 місяці тому
DIYer - not a cowboy one 😂 Out of curiosity: 1) tumble drier. Why C2 or C3 and not a misc observation. For example if everything is done correctly, would it not effectively just be treated as an extension lead? 2) Any reason for bonding a bathroom heater? Our house has bonded water mains, bonded oil inlet plus the bathroom heater has a bond.
@tobysherring1369
@tobysherring1369 2 місяці тому
1) because it's not 'the done thing' to put T&E into a plug (I'm not sure there's a reg forbidding it in this context) and it would be neater (and perhaps marginally safer) to put in a new fixed socket for the TD). Probably a C3 or observation, not a C2. 2) not sure what type of heater you mean, but a Class 1 appliance should always be earthed. It doesn't then need bonding as well under current regs. In the old days, metal in bathrooms was 'supplementary bonded' for additional protection before RCDs were common. A bathroom radiator similarly doesn't require bonding - either the whole water and/or gas installation is bonded at the incomer, because it introduces earth potential, or it isn't because it doesn't.
@cjmillsnun
@cjmillsnun 2 місяці тому
@@tobysherring1369 If it's on a plug it's not fixed wiring. You can make an observation only as the EICR is meant to only cover fixed wiring.
@tobysherring1369
@tobysherring1369 2 місяці тому
@@cjmillsnun I agree. I was trying to suggest why Artisan would code it - they made a worrying number of errors through this episode. They like to code things which aren't neat, or are unconventional, rather than dangerous or potentially dangerous. There's no regs about T&E in a plug, AFAIK, or clipping flex in an airing cupboard. I had an EICR done on a rental a few years back and they coded things outside their remit. Best example was 'no RCD to sockets that could be used for outdoors equipment'. It was a first floor flat! (I did a full RCBO upgrade but it shows how inaccurate they can be).
@kimmythesparks
@kimmythesparks 2 місяці тому
What is the tool you used to open the meter cupboard ? At 4:45 or so? Is it an attachment that goes into the interchangeable screwdriver ? 👏great video 🎉
@artisanelectrics
@artisanelectrics 2 місяці тому
Yeah it’s from my Wera interchangeable screwdriver kit
@tobysherring1369
@tobysherring1369 2 місяці тому
If you're testing the bonding as in your diagram, the separate path to earth (through the boiler's earth connection) will distort your reading, as did the boiler's connection between gas and water pipes. You are testing the boiler earth as well as the bonding cable. To test the bonding, disconnect it from the incoming water, gas or oil end, and measure resistance to the MET. You say there is continuity but there may not be from the cable...it could be broken and you wouldn't know.
@markrainford1219
@markrainford1219 2 місяці тому
For a 'how we do it' video, so many mistakes.
@AmperSam97
@AmperSam97 2 місяці тому
Actually an EICR is only required if you intend on letting out the property. There is no legal requirement for homeowners living at the address to have one.
@Spencer_White
@Spencer_White 2 місяці тому
Is insurance (generally) covering house if one not carried out within a reasonable time frame?
@tobysherring1369
@tobysherring1369 2 місяці тому
​@@Spencer_White I have been asked many questions when buying home insurance, but never 'has it had an EICR?'. It's clearly not a requirement of insurance. However if you or someone else did some dodgy electrics, that caused a fire, you wouldn't be insured. My old house had an EICR but since then the previous owner did many bodges; the only solution was to put it all right and have a new EICR to confirm the repairs.
@rogerbean393
@rogerbean393 2 місяці тому
Yes correct only if letting, more solicitors seem to be asking if properties are being sold , but it’s just a tick box exercise. Easy to scare homeowners into getting lots of extra work with reports falsely completed. Bet jordons mob was not £20 a circuit !!!
@samuel2j213
@samuel2j213 Місяць тому
You are right about there being no requirement for homeowners but why give your insurance company ammunition if something were to go wrong because everyone knows what insurance companies are like for trying everything to not pay out
@RobJowett
@RobJowett 2 місяці тому
Is the lack of RCD on lights actually a fail? If it's a design and install under the 16th edition, you didn't need RCD protection for anything other than sockets. Surely it's a note to say that the design doesn't meet the existing requirements under BS7671. Otherwise you'll have to fail a 17th edition install for not having a metal CCU.
@tonymcclave9198
@tonymcclave9198 2 місяці тому
I agree with C3 C2 is harsh
@davidfellick5171
@davidfellick5171 2 місяці тому
Agree this is not a C2 - this is an advisory. Listing as a C2 is profiteering. unacceptable. It should be flagged to customer but for them to decide as it's not a fail.
@jakebarrow2000
@jakebarrow2000 2 місяці тому
No it's not but these guys like the ££££s
@tonymcclave9198
@tonymcclave9198 2 місяці тому
Agreed My son had an EICR on his house by the purchaser. A NAPIT spark had 3 C2 's one for no smoke alarms one for gas bonding after a join one for light in garage without a diffuser offered to do remedials for £800-00 make your blood boil@@jakebarrow2000
@rogerbean393
@rogerbean393 2 місяці тому
It’s not a fail , it’s a report he’s generating. It can not be applied retrospectively. Nice earner scaring the customers with all these dangerous fails !!!!
@persona250
@persona250 2 місяці тому
There’s no way that unvented cylinder installed in 2014 is not going to have a thermostat and cutout . Just saying
@tobysherring1369
@tobysherring1369 2 місяці тому
If the Tesco plug meets BS1363 it's perfectly acceptable. It should be on a flex but is there a reg stating this?
@cjmillsnun
@cjmillsnun 2 місяці тому
It's technically not part of the EICR as because it's on a plug, it's not fixed wiring (same as that dodgy adapter in the batten light fitting in the loft)
@tobysherring1369
@tobysherring1369 2 місяці тому
@@cjmillsnun agreed. But if it was dangerous or close to being dangerous I'd note it. However, being snobby about a Tesco plug is unnecessary. An electrician could go to Tesco when the wholesaler is shut, to complete a job after hours. If it's wired correctly and not broken, with the right fuse then it would pass a PAT. Can you imagine how much Artisan charge for plugs?
@nathanvandenakker1278
@nathanvandenakker1278 2 місяці тому
In Belgium we do the isolationtest in a more simple way: trip the main RCD, then measure between the ground and the line / neutral. If the test is ok, there is nothing more to do about it, otherwise, trip all the fuses and measure every circuit.
@scottsaul
@scottsaul Місяць тому
What if you get a C1 and the client says that they will not pay for the problem to be rectified?
@michaeltye8853
@michaeltye8853 2 місяці тому
Must have missed the torque screwdriver being used to reconnect cables in consumer unit…😂😂😂
@mikeappleton7503
@mikeappleton7503 2 місяці тому
Do you get the clients permission to connect your laptop to their wi-fi whilst they are not home?
@waynerandall4036
@waynerandall4036 2 місяці тому
You do not have to have an EICR every 10 years if you own and live in the house/flat. It is just a recommendation or a money making scheme for electricians.😀
@Ragnar8504
@Ragnar8504 2 місяці тому
Looks like someone spends a lot of time grocery shopping in Austria 😀 Markthalle Kulinarium (the paper bags under the sink) is in Eisenstadt, less than an hour from where I live.
@shahab1964
@shahab1964 2 місяці тому
When you are doing IR test you are disconnected the earth from earth bar, is that correct or should left earth on earth bar and tested from there.(on 52 min)
@skelly8924
@skelly8924 2 місяці тому
It should be connected to the earth bar
@electricalstuff259
@electricalstuff259 2 місяці тому
Am i being dumb - why would flicking the light switch on or off affect earth continuity? Were you linked out in the board?
@samuel2j213
@samuel2j213 Місяць тому
R1+R2 carried out on the switch live so when switch is off you essentially remove the R1 from the R1+R2 so you wouldn’t get a reading , also how you prove the switches are working properly
@chrisfosbury5753
@chrisfosbury5753 2 місяці тому
Wow, haven't seen a bayonet light plug for a while, my grandmother used to plug her iron in with one!
@DavidMartin-ym2te
@DavidMartin-ym2te 2 місяці тому
So did my mum back at home in the sixties!
@rogerbean393
@rogerbean393 2 місяці тому
Dad used to run the Christmas lights of them and still in cotton braided cable. Probably still in the loft.
@thermion7869
@thermion7869 Місяць тому
They sure did live dangerously.@@DavidMartin-ym2te
@seanmacdonald8211
@seanmacdonald8211 2 місяці тому
The max Ze (0.35) you're referring to is at the origin of the installation. The board you're testing is not at the origin.
@chrispalmer9030
@chrispalmer9030 2 місяці тому
I’ve had a plastic water incoming pipe, but whilst testing found that I need to bond the internal pipes due to the pipe work passing through fabric of house
@persona250
@persona250 2 місяці тому
Hi Chris I don’t know of much internal pipe work not run within the fabric of a building . It only requires bonding if it introduces an earth potential . It would be difficult to introduce an earth potential without being buried in soil .
@tobysherring1369
@tobysherring1369 2 місяці тому
​@@persona250the point here is it needs to be tested for how much earth potential (ie resistance between it and MET. A pipe in contact with a damp wall in contact with earth could be an issue.
@Ben-gm9lo
@Ben-gm9lo 2 місяці тому
I hear you. I have plastic gas pipe feeding our house. My installer didn't want to install bonding. To my mind, the copper gas pipe connects to the boiler and then the central heating copper pipe. I know I have heating pipes under some of our concrete floors, so unless they are all perfectly insulated from the concrete (as they should be in an ideal world) my heating system is effectively grounded. For this reason I fitted bonding to my copper gas pipe.
@tobysherring1369
@tobysherring1369 2 місяці тому
@@Ben-gm9lo the installer can only make that call by asking an electrician to test and certify whether it introduces sufficient earth potential to need bonding.
@Ben-gm9lo
@Ben-gm9lo 2 місяці тому
Totally agree. This wasn't going to happen though, so I had to make a choice. He said if I wanted it done I would have to do it myself, so with his consent I grabbed his 10mm bonding from his van and bonded away! On balance I thought this was better than doing nothing, or waiting to recruit an electrician to come and see if it really needed it or not and then finding out it was needed.@@tobysherring1369
@Sixta16
@Sixta16 27 днів тому
1200: SELV is Safety Extra Low Voltage. You have shavers running at below 50V AC in the UK or what?
@simonr1392
@simonr1392 2 місяці тому
Smokes not part of eicr, it's BS5839. Wander lead is not required for metal fittings if you're doing R1+R2 at furthest point. Measured Zs will be different as you're measuring a live circuit which is an impedance measurement. Non live calculated Zs is dead which measures resistance. Interesting informative video though.
@TheJoeyDeacon
@TheJoeyDeacon 2 місяці тому
I guess the SELV mistake is easy to make, a bit like misusing the word Artisan……
@thermion7869
@thermion7869 Місяць тому
Nice one!
@andrebull2589
@andrebull2589 2 місяці тому
1:02:35 ish. Is it really 200ms for TN-c-s in the UK? It's 200ms for TT and 400ms for TN in Denmark :o
@swifty5783
@swifty5783 2 місяці тому
Its 200ms for an RCD with a BS number. Its actually 300ms for an RCD with a BSEN number at the rated trip current
@BluTrollPro
@BluTrollPro 2 місяці тому
Ahah, as a controls panel spark, I learn so much about how terrible my own domestic bodges are from these videos 😂
@blairfalconer915
@blairfalconer915 2 місяці тому
Should gas typically be bonded at the meter? The gas in my house is bonded where the supply enters the house (below the boiler). I can't see any water bonding but the supply is plastic so doesn't seem to be required going by what you said 👍
@joesouthgate
@joesouthgate 2 місяці тому
Within 600mm of the outlet of the meter before the first T or at the closest practicable point at which the gas pipe enters the property.
@blairfalconer915
@blairfalconer915 2 місяці тому
Thanks 👍
@tobysherring1369
@tobysherring1369 2 місяці тому
Only if the incomer is metal in contact with the ground, or another part of the gas installation is and doesn't have a plastic isolating section, and therefore introduces earth potential. This needs to be tested if in any doubt. You don't automatically bond all gas incomers any more. No (or miniscule) earth potential means no bonding.
@M0PAX
@M0PAX 2 місяці тому
R1+R2 test why do double the test? You go around with the wander lead and test that point then come back later and connect the live to CPC to test again. The record sheet has R1+R2 and or R2?
@samuel2j213
@samuel2j213 Місяць тому
Personal preference an R2 test can be used as you say but it seems in the video he was using it as a way to prove earth continuity to every metal fitting / faceplate without having to remove every metal fitting/ faceplate so you can take that reading yes but most people would do an R1+R2 over just an R2
@kevh3113
@kevh3113 Місяць тому
USB socket outlets regarding resistance testing needs to be taken into account !
@seanmacdonald8211
@seanmacdonald8211 2 місяці тому
The socket that supplied the drier isn't part of the fixed wiring. It's basically an extension lead. No code at all, worth noting at most
@eyazdani4537
@eyazdani4537 2 місяці тому
At 19:50, you noted 20 Ohms for TT system, which should be 200 Ohms.
@supremeicecreme1658
@supremeicecreme1658 2 місяці тому
Just an IT note from an IT pro... Why are you connecting to WiFi at customers' premises? I appreciate you're using a Mac, however that doesn't make you immune to everything. Anything that isn't your own should be considered untrustworthy so you definitely shouldn't be connecting corporate (loosely spoken) devices which touch sensitive customer data to these. Number 1 move would be to use mobile hotspots, which also means you don't *need* to keep the customer's kit powered up.
@alhughes9698
@alhughes9698 2 місяці тому
he forgot his tin foil hat too
@Gkkiux
@Gkkiux 2 місяці тому
Next episode: say hello to our new sponsor SketchyVPN!
@Lewdacris916
@Lewdacris916 2 місяці тому
yeah agree with you, should invest in a 5G hotspot so he is able to provide his own WIFI
@franklinodom4259
@franklinodom4259 2 місяці тому
Bet as an IT pro, you connect to your customers wifi :)
@rossedmond7852
@rossedmond7852 2 місяці тому
Geez... this guy is something else. Tell me ... has anyone else asked the customer "where is your gas and water bonding?" and not gotten a blank confused look... and a "I've no idea what youre talking about!" reply. what a fool! , not to mention assuming they are the best company around and the "Artisan way" is any different to any decent spark. what a fool!
@Joanddave
@Joanddave 2 місяці тому
Doesn't hurt to ask
@Spark101.
@Spark101. 2 місяці тому
Bang on point
@gdexterc
@gdexterc 2 місяці тому
No but it is reasonable to ask them, "Where is your water stop cock? and Where is your gas meter?" I think you should be careful calling others fools.
@Adam-TheSparky
@Adam-TheSparky 2 місяці тому
Ur videos are very educational ARTISAN team. Keep up the good work. I hope this changes the way the cowboy electricians approach jobs
@persona250
@persona250 2 місяці тому
1Mohm table 64 bs7671 .
@jonathanstephens7804
@jonathanstephens7804 2 місяці тому
are those downlights fire rated?
@artisanelectrics
@artisanelectrics 2 місяці тому
Nope
@jonathanstephens7804
@jonathanstephens7804 2 місяці тому
C2 or C3? @@artisanelectrics
@dmreichwein
@dmreichwein 2 місяці тому
Wonder why we don’t have something similar like an EICR in the Netherlands. Would be nice to see an abroad edition on a typical Dutch home installation with the pros and cons compared with UK.
@Ragnar8504
@Ragnar8504 2 місяці тому
No systematic testing and inspection? Germany and Austria have had that for decades but it was mostly only mandatory for commercial properties. Austria made EICRs mandatory for newly rented properties in 2008 and also added some requirements that go beyond "installations must comply with the regs in force at the time of completion", mainly 30 mA RCD protection for all circuits regardless of the age of the installation. I recently stumbled across a few videos by Dutch electricians and found some interesting differences in how things are done, like bare main earths.
@retrozmachine1189
@retrozmachine1189 2 місяці тому
A web search shows that you do have a testing regime but as with the UK it isn't compulsory for an owner-occupier of a private house to have it done, except in special circumstances. A good deal of the west is like that, inspections for rentals etc, and it's up to you to decide for your private house.
@Spark101.
@Spark101. 2 місяці тому
You also mention that the down light bezels 'technically' require an earth.....? They don't. Unless you can enlighten us as to why you think this? I assume you think they are an exposed conductive part? You would be wrong. The one other thing regarding those lights that you could have mentioned, which was more important, you didn't. I'm curious......how much is an EICR like this?
@tasslehoff1971
@tasslehoff1971 2 місяці тому
Regulations state that all circuits have a cpc run to all accessories regardless whether they are class 1 or 2. if its an old installation with plastic accessories then you can get away with putting a warning sticker on the DB.
@Spark101.
@Spark101. 2 місяці тому
@@tasslehoff1971 He said that the bezel requires earthing.....it doesn't. The CPC is there within the t&e...., just not connected to the bezel. Now if the CPC isn't adequately connected through, that is a different story, but earthing the bezel isn't required.
@tasslehoff1971
@tasslehoff1971 2 місяці тому
can you provide a time as to when he said that? I've heard him mention the metal clip that. but not bezel.
@tobysherring1369
@tobysherring1369 2 місяці тому
It's a simple matter of determining whether class 1 or 2. It's a black and white issue, no 'technically' about it: it either does (C2) or doesn’t (no code or observation) need the cpc connected.
@Spark101.
@Spark101. 2 місяці тому
@@tobysherring1369 I agree. It’s as simple as that.
@supersparks9466
@supersparks9466 2 місяці тому
Never do eicr,s hate them with a passion but someone has too do them I guess, will only ever consider empty properties and even then I have to give my head a wobble 1st
@tobysherring1369
@tobysherring1369 2 місяці тому
Priority Hot Water from solar is quite normal. Why is the contactor method wrong?
@benskidmore6523
@benskidmore6523 2 місяці тому
It's the "Loose breakers wired inside a project box" that's no good I imagine.
@muttlymoo
@muttlymoo 2 місяці тому
It's worth mentioning.. An Rcd test button should be pressed every 6 months as it stops the mechanism sticking when it needs to trip in the event of a fault No end of times ive tested an Rcd with a tester and it will fail to trip the 1x test the first time its tested because the mechanism hasn't moved for god knows how long.. Then once it it's been tripped once or twice it works fine
@andywindy
@andywindy 2 місяці тому
You forgot to qualify why many appliances have a small current to Earth, it is due to the L-C Suppression circuit at their mains inlet. Basically, there is a suppressor, consisting of an Inductor(L) and a Capacitor (C) between Live and Neutral, another between Live and Earth, and another between Neutral and Earth. On AC or Pulsed DC (as in many Insulation Testers) Circuits, a Capacitor conducts, as does an Inductor which is a type of Resistor. We used to have Pat Testers fail our smaller commercial equipment at one time quoting 'Live and Neutral short to Earth'. The Cooker should have had no earth leakage through the Elements or suppressors under the circuit test, as the Isolator should have been turned off, therefore Isolating it totally from the Phase and Neutral wiring! Keep going folks, for newcomers to the field, you do excellent work and explain things in English. I can't wait to see you Lads clipping 10 parallel runs of Bare Copper Pyro up a wall at 25mm spacings like I had to as part of my Practical finals at College! (Well, it Was in 1975.)
@spike9692001
@spike9692001 2 місяці тому
No RCD protection-Bathrooms C3 with supplementary bonding, cables less than 50mm C3, Bathroom luminaries C3, Insulation resistance values minimum of 1Meggerohm final circuits not 2 Meggerohms also CPCs should remain in the MET when testing, figure of 8 test1 & test 2 were the same?, ring main IR test no need to put both ends in the croc clips you just proven continuity, plastic incoming pipework- applying protective bonding to a conductive item which is not an extraneous-conductive-part might lead to the risk that under fault conditions these items may become raised to the fault voltage for the time it takes the protective device to disconnect.
@stunimbus1543
@stunimbus1543 2 місяці тому
33:31 that's where someone has converted a 12v downlight to a gu10
@simonb1996
@simonb1996 2 місяці тому
It's better to do that Insulation Resistance test with the CPC connected into the earth bar with all the other earths & CPCs.
@simonb1996
@simonb1996 2 місяці тому
Just seen that you do a Global IR test later on in the video 👌🏻 Isolate the Main switch though, so you don't get a dead short between the neutral & main earth (because of the PEN Conductor). You don't need to disconnect individual final circuit neutrals.
@simonb1996
@simonb1996 2 місяці тому
RCD 1x is within 300ms (not 200ms)
@simonb1996
@simonb1996 2 місяці тому
Great video though. Nobody can get everything perfect on camera/under pressure.
@joebristowtechnologicalbre2073
@joebristowtechnologicalbre2073 2 місяці тому
Always amazes me why it takes two sometimes 3 men to do an eicr. What happens when you have to pull in a big swa? 10 men? 20? Is the customer paying for two men to do an eicr?? And for it to fail giving you extra work? Ouch.
@dangraves7808
@dangraves7808 2 місяці тому
Single insulated exposed cables above down lights would be a c2 and therefore unsatisfactory, the fact that the bathroom light is not rcd protected is a c3 not c2 as the test is not retrospective and this would have complied with the regulations at the time of original installation
@scottsaul
@scottsaul Місяць тому
Can an electrician who has not got his test and inspection but knows how to do an EICR do an EICR thanks in advance.
@Spark101.
@Spark101. 2 місяці тому
Are you sure at 1 x the rated current on those RCD's, the reading shouldn't be greater than >300ms.........not the 200ms you stated??? Sorry mate, but I'd imagine this EICR has cost the customer hundreds, but in reality is worth little. lots and lots of mistakes.
@pmgc7539
@pmgc7539 2 місяці тому
Depends on the bs number of the RCD mate. Old RCDs (BS4293) need to trip within 200ms 👍
@Spark101.
@Spark101. 2 місяці тому
@@pmgc7539 Very true mate.....I suppose I am assuming that the RCD is BS61008. Being a 16th edition board, it could be either.
@Spark101.
@Spark101. 2 місяці тому
The BS4293 were replaced in around 2009 I think.
@Spark101.
@Spark101. 2 місяці тому
@@pmgc7539 Just looked....The one he tested was BS61008 🫣
@tasslehoff1971
@tasslehoff1971 2 місяці тому
replaced in 2000 and all production ceased by 2005
@tobysherring1369
@tobysherring1369 2 місяці тому
41.15 an RCD isn't connected to Earth so can't measure Earth leakage! It detects differences between line and neutral, and trips if the difference is above the predetermined current, because current is flowing where it shouldn't. Mowers and hedge trimmers should connect through an RCD but they almost never have a CPC.
@andywindy
@andywindy 2 місяці тому
This is why they stopped calling them ELCBs.
@tobysherring1369
@tobysherring1369 2 місяці тому
@@andywindy an ELCB does detect earth leakage, an RCD doesn't. They're two different things. It's like Jordan has forgotten basic things while he's been away.
@BenofYoutube
@BenofYoutube 2 місяці тому
3:26 should have said "it's megger".... I'll get my coat
@rafal8678
@rafal8678 2 місяці тому
Tesco plug top C2, are you sponsored by CEF Jordan?
@danvictor3934
@danvictor3934 2 місяці тому
Hi c2 For no Rcd Protection no way it is actually a c3 it even says so in Napit Codebreakers these regulations are not retrospective.
@tobysherring1369
@tobysherring1369 2 місяці тому
Feed from CU to solar? Surely that's a feed from the solar to the CU? And the 100mA RCD protects the installation, not the inverter, which only outputs AC (no AC input).
@caterthun4853
@caterthun4853 2 місяці тому
OK, as a customer you give me a certificate. All OK. But, what do I do with it. It will be 10 years until the next. If I loose the document about to sell house after say 5 years. Can I get copy if buyer asks for one..
@tomengineer1467
@tomengineer1467 2 місяці тому
You are supposed to keep certificates safe … with your home insurance file or home mortgage file ….. but no spark will give you a copy after a few years even 5 years you will need a new eicr as you don’t know if anything has been added or failed in that time
@alvina69
@alvina69 2 місяці тому
With most certification software, you can email reports and certificates to the customer so you’re always able to search your inbox and find it.
@mainlineelectronics5266
@mainlineelectronics5266 2 місяці тому
A broken ring final on a 32 amp breaker won't overheat and cause a fire.
@bobwalker7531
@bobwalker7531 2 місяці тому
Interesting. I am concerned that repeat testing will shorten the life of the installation. How many times can you remove and replace a wire before it is damaged. Is it possible to prove an installation is safe without removing wires or fittings? If you switch off an RCBO can you do insulation tests by connecting to the load terminals of the RCBO? Can you check resitance on ring circuit by observing voltage drop at a socket when a 3 kW heater is switched on. Some electricians could introduce faults when replacing wires or fittings! I think it shoild be possible to prove an installation is safe without removing wires and fittings.
@dangallagher2306
@dangallagher2306 2 місяці тому
I understand your concern but thi really isnt a problem as they done every 3,5 or 10 years
@user-uk3gc2dk3h
@user-uk3gc2dk3h 2 місяці тому
It's also pretty easy to re-terminate a wire, which might be fatigued from repeated removal and reinstallation.
@jeremykemp3782
@jeremykemp3782 2 місяці тому
@@dangallagher2306 exactly, if they did fuck something up, it would not be spotted for another 10 years lol
@dangallagher2306
@dangallagher2306 2 місяці тому
@@jeremykemp3782 and that would be down to that qualified electrician like any other time a mistake is made
@bobwalker7531
@bobwalker7531 2 місяці тому
By the time an introduced fault is found the previous electrician could be retired or deceased.
@dbtjambo
@dbtjambo 2 місяці тому
Cannot tell the size of the incoming fuse so should be noted as " not known"
@samuel2j213
@samuel2j213 Місяць тому
If the outside is marked as 100a you have to take that at face value as that is as far as we are allowed to go
@dbtjambo
@dbtjambo Місяць тому
@@samuel2j213 we were told at a "select" meeting that when filling in an eicr we had to fill it in as "not known"
@brianhannan2872
@brianhannan2872 2 місяці тому
YOU are certainly up for a sainthood make other spaks look humble.
@tobysherring1369
@tobysherring1369 2 місяці тому
I'd be very surprised if that's a traditional tank fed immersion system with a plastic feeder tank.
@brianoneill350
@brianoneill350 2 місяці тому
Guys all you are missing are the bullet proof vests. Thought I was watching the bailiffs collection programme 😂
@rogerbean393
@rogerbean393 2 місяці тому
For a video with more life and knowledge watch David Savery do an EICR
@davidunwin7868
@davidunwin7868 2 місяці тому
Luke rides the buzz to the bar.
@Mike_5
@Mike_5 2 місяці тому
EICR's down well by someone with knowledge are possibly the best thing you could ever pay for to protect your property and people in the premises from harm but done cheaply and badly can be your worst enemy
@markbriggs6786
@markbriggs6786 Місяць тому
Some of these fails are not fails it should be noted that existing installations apply to the previous regulation standards at the time of installation and upgrading to the latest regs is advisory . It’s not acceptable that some company’s jump on the money making band wagon and as previously stated home owners are under no legal requirement to have an ECIR . Saying that I would advise any home owner to have a periodic check done . The other problem is the ECIR is open to interpretation by the individual doing the test so standards are different and this is usually down to a poor understanding of the regs /electricity at work act and lack of experience .
@StaleEHuse
@StaleEHuse 2 місяці тому
At least a proper OSO water heater from Norway 😏
@kimmarshall5173
@kimmarshall5173 25 днів тому
RCD for lights on a 16th edition installation ! I think not, so never a C2, its not retrospective.
@Spark101.
@Spark101. 2 місяці тому
The long lead was incorrectly nulled. those R2 reading won't be accurate mate
@samuel2j213
@samuel2j213 Місяць тому
He didn’t use the R2 readings thought he used the wander lead to prove continuity but he did R1+R2 on each circuit
@Irilia_neko
@Irilia_neko 2 місяці тому
I think little skilled end user can do the first part, and the second part opening the electric appliances, it's free and can save a lot of money by correcting the basics fault like screw not screwed fully for example, for example also using a multimeter to verify earth phase, phase neutral, and earth neutral, to be sure there isn't a lost of earth or neutral. This is just basic test
@tobysherring1369
@tobysherring1369 2 місяці тому
A MFT is needed for the testing, eg insulation resistance and continuity of cables, earthing and rings. A multimeter measures resistance but not at sufficient voltage to give the required results. Sure, a homeowner can check for loose screws, cracked faceplates etc and check the basics, eg with a plug-in tester, but the value of an EICR is the stuff you can't test yourself. You'd have to read a lot to know what size tails and earth bonding are needed, and what needs bonding.
@Irilia_neko
@Irilia_neko 2 місяці тому
@@tobysherring1369 I never said it to replace the EICR I said if you don't have the budget, or anytime it a good idea to do it in place of doing nothing.
@tobysherring1369
@tobysherring1369 2 місяці тому
@@Irilia_neko yes, it's a good idea to test and repair what you can as you go along. But an EICR done properly gives you much more data and highlights things you could never find out for yourself. And sometimes you have to have one, eg rental property.
@TheEulerID
@TheEulerID 2 місяці тому
Even a 13A plug to a double socket wouldn't cause an overload due to the 13A fuse in the plug. Conceptually it is not really different to a power strip off a 13A plug, albeit that the strip will also have a 13A plug. Using T&E is a bit odd though.
@thomasdalton1508
@thomasdalton1508 2 місяці тому
It should be ok, but there is potentially a risk that the flex doesn't have adequate cooling in the wall. The 13A rating assumes they have air around them. That's why you shouldn't leave an extension cable coiled while in use. In this case, I can't imagine there being an issue, but it is something to think about.
@_chrisr_
@_chrisr_ 2 місяці тому
You are right, it’s just an extension cable, if the wire and socket weren’t clipped to the fabric of the house then it wouldn’t be within the scope of the regulations but as soon as it becomes “permanent” they apply. This is why extension cables with holes for screws to attach them were banned in uk back in late 80s or early 90s.
@johnwarwick4105
@johnwarwick4105 2 місяці тому
@@_chrisr_really 😳every 4 or 6 gang lead still has two fixing holes.
@johnwarwick4105
@johnwarwick4105 2 місяці тому
@@thomasdalton1508overheating! It’s 2.5 on a 13a fuse come on
@davideyres955
@davideyres955 2 місяці тому
The problem with T&E is it’s solid core. When you bend and move around solid core it work hardens and cracks changing the resistance of the cable. Over time this “could” reduce the current carrying capacity of the cable to be less than the fuse. I think this would take a lot of time to be dangerous but it’s possible. In the IT world using solid core in patch leads eventually fail but as the voltage is very low any minor change can cause problems. Sure they work but they do fail within a few years. However the risk is really small.
Nearly KILLED by a CRAZY fault! What on earth is going on? 💀
27:12
Artisan Electrics
Переглядів 669 тис.
WORST DIY ELECTRICS I'VE EVER SEEN! 🤯
22:52
Artisan Electrics
Переглядів 635 тис.
Physics Practical on Electricity. Waec 2024.
32:50
VINDAL'S ACADEMY
Переглядів 16
I took on an IMPOSSIBLE job... what was I thinking??
18:37
SOTA Electrical
Переглядів 20 тис.
This Is Why Builders SHOULDN'T Do Electrics! 🫣
19:59
Artisan Electrics
Переглядів 59 тис.
Have We Been Doing Solar WRONG All Along? 🤷🏻‍♂️
19:48
Artisan Electrics
Переглядів 96 тис.
SHOCKING FIND - SO bad I had to fix it IMMEDIATELY
25:16
Artisan Electrics
Переглядів 187 тис.
RETURN TO THE WORST REWIRE!
28:11
SOTA Electrical
Переглядів 19 тис.
Fault finding on a Ring Final Circuit using R1+R2 & R1+RN, the only way to prove polarity AM2 AM2S
19:09
Pure Electrical Training - by Adrian Davey
Переглядів 37 тис.
10 Mistakes EVERYONE Makes When Doing DIY Electrics!💥
11:56
Artisan Electrics
Переглядів 140 тис.
CHEAP Electrician cost this customer £1000s💷
18:43
Artisan Electrics
Переглядів 106 тис.
Индуктивность и дроссель.
1:00
Hi Dev! – Электроника
Переглядів 102 тис.
wyłącznik
0:50
Panele Fotowoltaiczne
Переглядів 2,8 млн
Эффект Карбонаро и бумажный телефон
1:01
История одного вокалиста
Переглядів 432 тис.
How Neuralink Works 🧠
0:28
Zack D. Films
Переглядів 26 млн