Is water in plastic pipes conductive?

  Переглядів 36,354

John Ward

John Ward

6 років тому

Water inside a plastic pipe is tested for resistance at various voltages.
15mm diameter PEX pipe, 1m length, normal tap water.
Another test with AC rather than DC: • 240V AC vs water in a ...
Support this channel at Patreon: / jwflame
Twitter: / jwflame
Facebook: / jwflame
Instagram: / jwflame
Contact info, sending stuff in etc.: xo4.uk/?YTT

КОМЕНТАРІ: 205
@allthegearnoidea6752
@allthegearnoidea6752 6 років тому
My grandparents had a very old house with an electric water heater in the bathroom. Looked like something from a Frankenstein movie. The control box had two enormous neon indicators that would glow a satanic pink and terrified me as a kid. Anyway I pulled it apart when they modernised the bathroom and the water ran through an exposed wire element. This thing had been in service for not much less than 100 years I imagine. They don’t make em like that anymore. They had a mixture of rubber cotton wiring and even some wood covered cable. Was still all in service in 2000 when the sold and moved out. They also had the remains of a generator in the cellar. All the rooms were enormous with servant bell. The whole house was really creepy
@croydonvideo
@croydonvideo 5 років тому
This reminds me of an experiment I did (unwittingly!) many years ago. A CT system running at 120KV with about 100mA normal current in the xray tube, suddenly overloaded and the system turned off. (With a loud bang 😀 ). No problem could be found and when switched on it operated normally. It did this once a week for a number of weeks. Each time it was reset it operated normally for days or even a week. I eventually traced it to water in the cooling oil of the xray tube. The oil was pumped into a heat exchanger which was water cooled. The cooling water then run to waste. Little holes had developed in the exchanger and eventually the oil was replaced by an oil water mix. It shows the water in Melbourne Australia is quite soft with minimal contamination!!!
@Clip7heApex
@Clip7heApex 6 років тому
I suspect the reading could be vastly different with an old pipe containing mineral deposits along the inside surface. Also water from different areas having different dissolved mineral contents. I've seen the inside of plastic pipes stained blue with copper from old copper hot water tanks. Interesting experiment all the same.
@iiiiiiicurtisiiiiiii
@iiiiiiicurtisiiiiiii 6 років тому
very interesting john, always wanted to this. been watching your videos for a while now. you seem to answer all of the nice to know questions !
@gartmorn
@gartmorn 5 років тому
In the power station we used demineralised water to cool the stator windings which were at a potential of 17kv! The core tubes were fed via PTFE pipes not dissimilar in appearance to the pipe in the video.
@davidblyth5495
@davidblyth5495 Рік тому
We also used such water to cool the anodes of high power radio transmitters. I can't remember the voltage but the power output was 50 kW
@gwynnej3
@gwynnej3 Рік тому
@@davidblyth5495 i guess with DC you want as low conductivity in the water as possible otherwise you'll electrolyse it to hydrogen and oxygen.
@davidblyth5495
@davidblyth5495 Рік тому
@@gwynnej3indeed. The water was highly purified as it had to act as a coolant and isolator
@kylebishop6233
@kylebishop6233 6 років тому
0:33 JW, strokes his solid pipe! 🤣
@fieldsofomagh
@fieldsofomagh 6 років тому
Very thorough experiment with all the variables accounted for. Job well done.
@skysurferuk
@skysurferuk 2 роки тому
Interesting practical demonstration.
@DsaTechnicalSolutions
@DsaTechnicalSolutions 6 років тому
nice video jw , informative as usual
@jpcvandam
@jpcvandam 6 років тому
So the conductivity of your drinking water is about 560 uS/cm which is quite normal. Nice video it made me realize that potential equalizing is essential in modern installations because the pipe isn't conductive anymore.
@tammmacdonald7723
@tammmacdonald7723 6 років тому
Would have been interesting had you checked the pipe empty first. Some type are conductive.
@onlythetruthfull
@onlythetruthfull Рік тому
This reminds me of when I moved from an area of soft water to hard water, it took a lot of getting used to, more washing powder, washing up liquid, and shampoo. The water was so hard I even had to wear a crash helmet in the shower.
@Cavalier_Steve
@Cavalier_Steve 6 років тому
Nice video John, very interesting.
@paulmorrey733
@paulmorrey733 6 років тому
Thanks John
@timperkins6665
@timperkins6665 5 років тому
Thanks John. I was taught that about 1 m of 15mm plastic is enough to turn exposed metal to extraneous. Given the figure of 23kohms minus 1 k ohm for dry skin you'd need slightly more than 1 m between the earthed pipe outside the bathroom & the touchable metal pipe above the floor to omit supplementary bonding with your figures. Apparently that figure doubles when you have central heating additive and doubles(approx) again for 22mm. So an "insulating insert" on the incoming water at POE under the is going to need to be approx 2.5 M to be truly insulating. Did i do my maths right or have I missed something?
@martinwinfield2935
@martinwinfield2935 6 років тому
Very informative demonstration thanks. This could answer something that has puzzled me where firemen poring water onto a building never seem to worry about the electrical cables inside that are live.
@starman_uk
@starman_uk 6 років тому
Normally the DNO will isolate the wider electrical network in the street.
@NOWThatsRichy
@NOWThatsRichy 6 років тому
That another thing, years ago on the front of shops there used to be the 'fireman's switch' that they could turn off the power in the event of a fire, but you don't see them much nowadays.
@dandel351
@dandel351 6 років тому
That's a very interesting video there John. Kind of relevant in my neck of the woods at the moment. I've been reading in the news about a young girl in Western Australia who was electrocuted after going to turn off a garden tap while standing in a puddle of water. The poor girl somehow got full mains voltage at 240v applied to her. The news article mentioned an open circuit neutral was to blame I think. The girl survived the shock but she is now blinded and has other serious injuries, and at first she wasn't expected to survive at all. I'm not sure how that works in that a garden tap can become live without it blowing fuses or tripping some sort of circuit breaker.
@jwflame
@jwflame 6 років тому
Probably what is described in this video: ukposts.info/have/v-deo/goJ5raemrICB23k.html where the incoming supply combined N&E conductor is broken but leaving L connected.
@warrengray610
@warrengray610 6 років тому
Hi John, interesting video, I am curious as to why the voltage on the fluke meter was limited when you tested with both the 500v and 1000v ranges, Also if A.C. were flowing what would happen? Kind regards Warren
@simonparkinson1053
@simonparkinson1053 6 років тому
Warren Gray The device test current is limited to 1.5mA on all insulation ranges - which may tingle but won't be fatal. So with a resistance of 190k ohms , a current flow of 1.5mA will produce a voltage drop of 285V. The voltage on the 250V and under ranges cannot produce a current flow of 1.5mA through 190k ohms, so the voltage is not clamped by the current limiting. When you test a cable, the cable resembles a capacitor with a very high resistance connected across it. The Megger will output 1.5mA to charge this up, you see the displayed resistance and voltage increase as it charges - until the capacitive element has charged and the only current flow is through the leakage resistance. That's why it's also important to let go of the test button or release the lock to discharge the cable before disconnecting the test leads. That charged up cable can produce a far higher current through you than the Megger itself can - and can also damage the equipment you connect.
@warrengray610
@warrengray610 6 років тому
Simon Parkinson Thanks Simon, that explains it, Re:- capacitive charge,, I always ensure that I discharge motor capacitors or any significant source of stored charge when investigating white goods, usually these will be designed to self discharge, but hey better safe than sorry it's just an ingrained habit now after the early days of studying C.R.T.'s Where I removed the rubber cover from the back of the screen and got a hell of a jolt Even through the T.V. had been unplugged most of the day! Thanks my friend Good to share points with eachother Kind regards Warren
@sbusweb
@sbusweb 6 років тому
+John Ward So, question is, what are the risks of conductive water across an "insulating"-section? e.g. Can you start electrolysis of water, create hydrogen and oxygen? Will a shorter "insulating insert" still be 'safe' from the point of view of avoiding equipotential-bonding of a supply-pipe --- 5cm "insulating insert" with 230v across might give 25mA ? [a change in 18th edition may be coming in this regard?]. The danger comes from introducing a potential via the water when this was assumed not to be possible? Current-flow through your body through 180k resistance (for this length) was mentioned, but when would that situation occur -- only with lost-TN-C-S neutral scenario?
@Mark1024MAK
@Mark1024MAK 6 років тому
sbusweb Metal pipework (including sink units) is supposed to be bonded to earth wherever there is a risk of an electrical appliance causing it to become live.
@sbusweb
@sbusweb 6 років тому
+Mark 1024MAK Thats' different, thats' about bonding-to-earth, in which case the danger is more like -- there BEING an insulated-section and no low-impedance-path to earth. See: supplimentary equipotential bonding [John's video ukposts.info/have/v-deo/e4apdpurq4ehsYk.html ].
@tomorichard
@tomorichard 6 років тому
Lost pen conductor or possibly high earth potential caused by a fault leaking to common ground earth via supply transformer, Internal resistances created within the property will be completely safe as long as they are not resistances referenced to the mass of the earth
@tomorichard
@tomorichard 6 років тому
Mark 1024MAK this is classed as earthing and not bonding and is only required if separation between main voltage and pipe work can not be avoided in which case the pipe work must achieve automatic disconnection of supply
@darkknight145
@darkknight145 6 років тому
Would be interesting to check if there is a difference in the resistance when the pipe is pressurised and unpressurised, also with different waters, ie. rain water which should be a much higher resistance.
@ladams5356
@ladams5356 Рік тому
Hey John old one I know . How come we have tripping issues with joint boxes poorly sealed and water has got in ?
@tomorichard
@tomorichard 6 років тому
This is good example of why just because an incoming service supply is in plastic doesn’t automatically mean that protective binding is not required, as depending on the way a water pipe/gas pipe is installed a dangerous level of earth potential can still be picked up inside the property. Under 23k to earth based on 10ma current And also why addiction supplementary bonding may be required via high resistance plastic joints
@mmh1922
@mmh1922 Рік тому
Very interesting, thank you.
@no_short_circuit
@no_short_circuit 6 років тому
John, thanks for the video. Not an electrician but work as a mate (something to do in my retirement from industry). I've been studying your videos on Equipotential Bonding and don't fully understand the theory of it it all yet. Where does this video leave me if in a bathroom (say) the pipes under the floor are copper but change to plastic to feed the wash hand basin?
@muzikman2008
@muzikman2008 6 років тому
GrumpyGrampa you do not need equipotential bonding to plastic pipe.. Only the metal or copper part where it leaves the meter... If it's there. Same with gas pipes.
@no_short_circuit
@no_short_circuit 6 років тому
Thanks muzikman2008. I think I get that but if you bond there what about the wash hand basin taps that are metal fed by copper from the mains then plastic under the sink?
@Psychotol
@Psychotol 2 роки тому
How hard would the water need to be before it does start to get dangerous? (or would the water hardness itself be a bit more dangerous before the electrical hazard becomes significant?)
@eazthitman
@eazthitman 4 роки тому
Hi John, does this mean that supplementary bonding is not required to the metal parts if they are isolated by plastic pipes at both ends?
@andyxox4168
@andyxox4168 2 роки тому
Read the Wiring Regulations and you will know ...
@Dranok1
@Dranok1 2 роки тому
Interesting result, I wonder if it is because you have static water -- it has been shown repeatedly that a moving column of water is conductive enough to be significant. I was fault tracing some years ago in a restaurant bar where "potential shock risk" was reported (i.e. current above threshold of perception making the "ordinary persons" fear for their safety). It turned out the taps on the sink hiding under the bar gave a perceptible tingle especially when they were running. 100% inspection to every accessory on, under, behind and over the bar area showed that the bar was a later addition to the restaurant and installed almost like a prefab module, sitting atop the vinyl fake wooden floor and totally insulated from the room but with potential for static build up everywhere. numerous fridge units (compressors) and other Class 1 stuff like the glass washer and a few switch-mode psu's (the EPOS and others). No bonding in the whole area because the installer clearly didn't see a need. The supply to the sink was plastic, and GN8 of course tells us that if doing an R2 test (wandering lead back to the MET) shows a resistance >2kΩ then we can consider that item not to an extraneous-conductive-part. So when I dabbed between the taps and the CPC of the closest accessory (a worktop socket) I saw only 2-and-a-bit kΩ, but when I turned on the taps and let them flow at a decent rate, it dropped to a bit under 2kΩ. I added local equipotential bonding and the problem vanished. TL;DR: classroom maths theory or a carefully controlled lab experiment, like this, shouldn't always be taken at face value. The theory is sound and demonstrated well (I'm especially a fan of the old Fluke 1653 with the Robin branding proudly in place;-) but field experience can differ significantly due to many other influences... For instance,the contentious new Reg's regarding incoming services with a short "insulating section." It is no longer necessary to apply equipotential bonding (although confusingly it doesn't say that main bonding is unnecessary). Do you bond it anyway? Depends on if there any issues in the property. Yes? Bond the damned thing! No? Don't bond it in case you introduce a ground potential that wasn't there before.
@ColinDH12345
@ColinDH12345 6 років тому
What does this same about bonding a house installation when all of the pipe runs to a bathroom, for example, are plastic whist there may be metal parts in that bathroom. Is it still necessary?
@jwflame
@jwflame 6 років тому
Bonding not required with plastic pipes, and even if you wanted to, connecting wires to plastic would do nothing. Bonding is only required for conductive items which originate outside the room and could bring a potential into the room - pipes being the most usual example. A tap at the end of a plastic pipe won't introduce any potential - it's no different from a metal hook on the wall or a metal door handle.
@ColinDH12345
@ColinDH12345 6 років тому
My thinking for asking the question is that often copper is used for the last part from behind the wall up to the taps for example. In that case could the copper be deemed to originate from 'outside the room'. Also, although we know it comes from juts behind the plasterboard, someone inspecting may not know that and expect to see bonding on the last run of copper thats visible. Great videoas John. I've watched them all. You have a clear presentation style which is great. Thanks for taking the time to create them and answer the occasional question.
@lordmuntague
@lordmuntague 6 років тому
This is seriously good stuff. No need for paranoia next time I shower (by coincidence the same Triton Cara model that Big Clive did).
@warrengray610
@warrengray610 6 років тому
Hi John, 2 bar is quite substantial! Kind regards Warren
@ianlouden7939
@ianlouden7939 4 роки тому
2 bar is a normal figure, i think it can be upto 6 for a domestic property?
@erlendse
@erlendse 6 років тому
I would like see what happends if the voltage is applied over time (also AC vs DC). (maybe even fill in on some common faults that can lead to it) Just the basic circuit: water mains on one end, closed tap on the other. The pipe in the video is a good model for that (maybe add a overpressure valve.. tho)
@TheJHSound
@TheJHSound 6 років тому
Realy interesting video!
@MultiOutdoorman
@MultiOutdoorman 2 роки тому
must admit i always did wonder... thanks
@tomschmidt381
@tomschmidt381 6 років тому
Interesting test, I'm surprised the value was so low. Wonder how much this will vary depending on the water supply.
@crazygeorgelincoln
@crazygeorgelincoln 6 років тому
That horrendous solid plastic mega looks great. Has it had a video of its own.
@jwflame
@jwflame 6 років тому
Shown in this video: ukposts.info/have/v-deo/gZSQgml5aH2r1Z8.html from about 6 minutes in.
@crazygeorgelincoln
@crazygeorgelincoln 6 років тому
John Ward ace!
@21trips
@21trips 3 роки тому
Can you send a tone down a water pipe using a transmitter so that it can be located with a locator?
@brainndamage
@brainndamage 6 років тому
In our location most of new tap water installations that use PEX use PEX-AL-PEX which has an inner aluminum vapor barrier, surrounded by PEX. The Al doesn't come in contact with the water normally and the fittings also don't make contact so in effect the pipe is nonconductive when new. The question is, what would happen when over many years perhaps the inner plastic layer cracks? This would lead to the pipe effectively becoming conductive, would the pipe be treated as conductive ie. requiring bonding?
@darkknight145
@darkknight145 6 років тому
Also a layer of salts/minerals deposited on the inner walls of the pipe.
@jwflame
@jwflame 6 років тому
The barrier pipe is used here as well (that in the video is the barrier type). The inner and outer are the same material, so it's not likely for one side to fail and leave the other side intact - any kind of crack would result in the pipe leaking.
@nickcollins7568
@nickcollins7568 6 років тому
Very interesting. Should repeat the experiment with the pipe then drained of water.This would act as a control to see how much effect the water has
@mixerfistit5522
@mixerfistit5522 6 років тому
Nick Collins an empty plastic pipe would read infinite / open circuit.
@erlendse
@erlendse 6 років тому
You mean like totally dry inside? or wet but not filled? PEX is also used to isolate high-voltage wires.
@jwflame
@jwflame 6 років тому
I'll show that in a future video, but even immediately after removing the water (inside still wet), the resistance is over 1000MΩ with a test voltage of 1000V.
@stefantrethan
@stefantrethan 6 років тому
There are now many instant water heaters on the market that have a bare (uninsulated) heating wire exposed to the flowing water. Before and after the heating element there are serpentines built into the plastic so you get a certain length of water column for insulation. The installation instructions specify you may only use them up to a certain conductivity of the water and to inquire with the water company if you are unsure. These are fully certified units for the european market made by top brands, not some chinese Ebay crap, the Stiebel Eltron DNM 4 is one example. You can find a schematic picture if you google "blankdraht heizsystem". It scares me a bit, what if you are in the shower and some contamination comes through the pipe. I hope they put a grounded section at the output!
@michaelcostello6991
@michaelcostello6991 2 роки тому
Have you a video showing how water is so dangerous in shower or bath. Thanks for this video
@Droningonuk
@Droningonuk 6 років тому
Can u run the test again with 22mm pipe to see how much better the resistance would be?
@WildMidE
@WildMidE 5 років тому
water between two rods make very large capacitor, so when you use AC voltage the condectivity very high
@pb5640
@pb5640 Рік тому
Pure water i.e. distilled water has very high resistance and can essentially be considered non-conductive. It’s all of the minerals, chlorine and other contaminants that makes water conductive. Pressure will also decrease resistance to a small degree.
@silenzzio
@silenzzio 6 років тому
Good to know👍
@TheDickPuller
@TheDickPuller 6 років тому
With the water in a plastic pipe only conducting a very small amount of current, is there any point in bonding the copper tube section on an incoming water main, where it’s entering the building in MDPE or any other plastic? Maybe I’m being simplistic, but I thought it was to ‘ground’ a faulty system? Thanks John very interesting as always👍
@jwflame
@jwflame 6 років тому
Probably not. If it's not an extraneous conductive part (something which can introduce a potential from outside), then it won't need bonding.
@starman_uk
@starman_uk 6 років тому
I had experience of fault on a persons installation causing "tingles" while showering - could make a crude joke but I shall restrain myself.
@vkman34
@vkman34 5 років тому
So what are the implications for earthing points? A lot of houses use copper water pipes as an earthing point, but if there's a plastic section in the pipe between the earth point and the mains water inlet, it's no longer providing a good ground connection right?
@jwflame
@jwflame 5 років тому
Water pipes should not be used as the earth (not permitted since the 1960s), however metal pipes usually need to be bonded, which although connects them to the earthing terminal is not earthing. If the pipe has a plastic section, it does not need to be bonded.
@jonbarnes9410
@jonbarnes9410 4 роки тому
Thanks John interesting. What would happen if you just replace a copper fitting with a push fit plastic fitting. Would this have implications to the earthing arrangements within your property.
@jwflame
@jwflame 4 роки тому
No difference to earthing, but might make a difference to bonding. Earthing and bonding are two entirely separate and different things.
@jonbarnes9410
@jonbarnes9410 4 роки тому
Yes exactly what I was trying to imply. Many properties with leaks on copper Hot and Cold water supplies are being repaired with push fit plastic fittings surely this could effect the bonding effectiveness. What would be the recommendations from a plumbing repair perspective ie cross bond across fittings or this would not be necessary. Thanks
@andyxox4168
@andyxox4168 2 роки тому
Not required, read the regulations ...
@Elec-DIY
@Elec-DIY 6 років тому
I sometimes get statically charged and open the water tap in my kitchen, only getting a shock when I touch the water stream, instead of the metallic handle. Isn't that weird?
@DGTelevsionNetwork
@DGTelevsionNetwork 6 років тому
ElecDIY There could be a ground fault somewhere in your supply. Do you know if you have all metal pipes?
@heronimousbrapson863
@heronimousbrapson863 5 років тому
ElecDIY I've had the same experience. My potable water pipes are copper.
@Coolkeys2009
@Coolkeys2009 6 років тому
I think you would definitely feel the wobble from >1ma, you can often feel current in the micro amp range from the leakage in transformers and AC adapters with the back of your hand.
@Mark1024MAK
@Mark1024MAK 6 років тому
Coolkeys2009 What about the leakage from Y rated suppression capacitors in class II devices or PSU? I can feel that current.
@MARKKY2727
@MARKKY2727 6 років тому
if you where somehow within that water filled plastic pipe the current through your body would be less as your human body has added resistance.
@Mark1024MAK
@Mark1024MAK 6 років тому
marc Only dry skin has any significant resistance. Wet skin allows electrical current to enter the body. Then once inside, the tissue is more conducive than that of the water on the outside.
@MARKKY2727
@MARKKY2727 6 років тому
Mark 1024MAK yes but your effectively in sereis with load so only less current can flow. Ie if your somehow inside the water filled plastic pipe.
@Coolkeys2009
@Coolkeys2009 6 років тому
If you are in series with a 1ma current flow 1ma of current will flow through you, the size of contact surface area will probably also affect how bad it feels though.
@SproutyPottedPlant
@SproutyPottedPlant 6 років тому
Would it still trip the RCD if rain water got into the back of a socket from a leaky roof?
@jwflame
@jwflame 6 років тому
Very likely. At the back of a socket the distance between L&E is tiny and there is likely to be dust or other contamination present which would increase the conductivity of the water.
@Elastane
@Elastane 6 років тому
interesting, thank you.
@rossaindow4390
@rossaindow4390 6 років тому
Could you do a video giving advice to young apprentices, i've just finished my level 3 qualification and i'm hoping to get an apprenticeship to become more qualified as an elctrician e.g AM2, electricians card, 18th edition ect. love your videos
@GretatheEvilGremlin
@GretatheEvilGremlin 6 років тому
Look on JIB website Ross. That`s the best way to determine where you stand with courses and qualifications to be recognised with a grading. Personally I think it`s turned into a shambles, but you got to toe the line, and at least get a JIB graded card. Always worth developing into inspection and testing tho, get yourself off the tools, and look to supervising and project management. Good luck with it.
@rossaindow4390
@rossaindow4390 6 років тому
Thanks a bunch I'm close to getting an apprenticeship with a local company i'm 18 years old and i've only got my level 2 and level 3, do you how long roughly it would take to become fully qualified ? as in full level 3 nvq, 18th edition and AM2
@GretatheEvilGremlin
@GretatheEvilGremlin 6 років тому
All things being equal, you should be 19/20 when it`s all done. Not an expert with this NVQ stuff, am old school City & Guilds. But if you`ve already completed Level 3 (to 17th Edition) I would expect you only need a refresher and brief exam to obtain 18th Edition. It`s only the same when 17th came out, those who had recently passed the 16th, did a one day course and a 30 question exam. See what the structure of 18th Edition accreditation brings. Hopefully you get that apprenticeship, give it 12/18 months in the workplace, then wrapping the AM2 up should be a cakewalk. You done the hard part, finish line is in sight.
@Benzknees
@Benzknees 2 роки тому
And if a metal (lead) main is attached to a plastic street main?
@lordbyrom100
@lordbyrom100 2 роки тому
I worked on a shower unit where the element was in a clear plastic tube inside the enclosure .I removed the cover to test voltage and resistance and finally restored the supply the local means of isolation was in another room (eg through the wall from bathroom to kitchen )however when I returned the valve had failed to open and the element had melted the tube in less than 20/30 seconds max .The resistance of the water must have been similar to that on this test and added to that the resistance of the element !!!Not a good set up and this was before RCD protection !!
@onlythetruthfull
@onlythetruthfull Рік тому
Which is why you don't get electrocuted when your immersion heater rots away
@paulbritton187
@paulbritton187 2 роки тому
As long as the pH of the water stays below 7, the water won't become conductive. I worked on a HPA using a water cooled tetrode, it had a long coil of rubber hose carrying the cooling water and pH monitoring. If the pH rose the 20kV+ anode voltage would start to get shorted to earth down the water column in the hose.
@andyxox4168
@andyxox4168 2 роки тому
Rubbish, please go back to school!
@steviecandtheplace2b
@steviecandtheplace2b 6 років тому
what about the same test with flowing water?
@jms019
@jms019 5 років тому
The upshot is if your leccy shower somehow goes live and your bath has plastic pipes and there are no earthed metal pipes to touch you should get no more than a tingle
@michaelcostello6991
@michaelcostello6991 2 роки тому
There was an electrocution on internet where unearthed metal/pole lamp holder in garden became live at a pub. I think water got into the lamp. Can this cause the metal pole/lamp holder to become live and allow enough current to pass to kill. Probably very little distance between the live wire and the metal lamp so water resistance might be a lot lower than your experiment in this video. Could you do a video on this ??
@SteS
@SteS 2 роки тому
David Savery has done a video on this.
@calebbrookes7896
@calebbrookes7896 Рік тому
Why would the tester not test the full 500 or 1000v?
@abyssalreclass
@abyssalreclass 6 років тому
2 bar is approximately 29.4 PSI IIRC
@muzikman2008
@muzikman2008 6 років тому
Conductivity depends on the minerals in your water supply as John said, . Add salt and watch its resistance drop dramatically 😉 there's another video..
@ianlouden7939
@ianlouden7939 4 роки тому
A human would feel 1mA but it wont kill, if you had used pure water (as pure as they use to jet wash extra high voltage power lines) it would not conduct, how water conducts is hugely dependent on its purity, some areas will be worse than others! It would be interesting to know if an old pipe with a lining of "crust" performs any differently?
@victorlibo8236
@victorlibo8236 5 років тому
Hi JW, thank you for all your very valuable and education videos. In one of your videos you introduce different amperages on a conductor to test connectors. What device are you using for different amperages ?
@jagardina
@jagardina 5 років тому
Throw some table salt in the water for a completely different result. And watch out for hydrogen/oxygen being created.
@Bodragon
@Bodragon 6 років тому
Chic sandals. Nice.
@daveaustin53
@daveaustin53 5 років тому
So those tests were made with direct current, giving an idea of the water resistance. But of course the mains is AC - so it would be interesting to see what current would flow through the pipe with an AC test current?
@jwflame
@jwflame 5 років тому
AC tests are in this video: ukposts.info/have/v-deo/a11kgWmpbW-hsIU.html
@Pithead
@Pithead 5 років тому
The closed pipe isn't pressurised at 2 bar. The pressure from the hose going into the pipe was at 2 bar.
@andyxox4168
@andyxox4168 2 роки тому
Really ... 😂😂😂
@mrtechie6810
@mrtechie6810 Рік тому
That would depend on the ion content of the water!
@KBilt92
@KBilt92 6 років тому
If you dissolve lye in there you'll have a very conductive aqueous solution - but even that wouldn't compare to copper or aluminum at the same cross sectional area.
@joinedupjon
@joinedupjon 6 років тому
What's that 'robin' logo on the fluke megger? was very pleased to see the reappearance of the wind up chinese item btw... more cranking of handles = more entertainment thanks for that.
@jwflame
@jwflame 6 років тому
Robin was a separate company which designed test equipment and had it manufactured by Kyoritsu. Robin was then taken over by Fluke who used the Robin name on some of the Fluke products for a while. What wasn't obtained by Fluke ended up as Kewtech, who still have their products manufactured by Kyoritsu. That's also why some of the Robin products and the early Kewtech products look very similar other than the colour changing from yellow to grey.
@R4MP4G3RXD
@R4MP4G3RXD 6 років тому
What about flowing water?
@PlasmaHH
@PlasmaHH 6 років тому
2bar isn't really that much, is it the normal pressure you have over there?
@jwflame
@jwflame 6 років тому
It has been higher, it was about 4 bar once, but has reduced to about 2 or 3 now depending on the time of day. 2 is still well above the minimum requirement so the water company won't do anything.
@PlasmaHH
@PlasmaHH 5 років тому
Interesting, while the minimal pressure here is 1bar it is only allowed for "difficult installations" and the general requirement is that it should be about 8bar and not lower than 6bar for almost equal level installations.
@MajorBloodclot
@MajorBloodclot 6 років тому
Obviously a video for the ladies - John Ward wears figure-hugging t-shirt and manhandles his impressive pipe
@kylebishop6233
@kylebishop6233 6 років тому
EvilabodeProductions lol love this comment! 😂
@patdbean
@patdbean 6 років тому
Would it be any different with distilled water?
@Mark1024MAK
@Mark1024MAK 6 років тому
patdbean Yes, the lower the impurities, the lower the conductivity. That's why demineralised water should only be used to top-up wet lead acid cells.
@BearsTrains
@BearsTrains 6 років тому
Distilled water is an excellent insulator. There are bore pumps where the motor is actually filled with distilled water for cooling
@cspower7259
@cspower7259 6 років тому
Wonder how well it would work as a load.
@wisher21uk
@wisher21uk 6 років тому
I notice the "GENUINE PLASTIC SCREWS" on the megger screen surround Nice .......😂😂
@ianstevens3581
@ianstevens3581 6 років тому
It’s not a Megger ,it’s Chinese brand . Megger is a trade mark name
@freesaxon6835
@freesaxon6835 6 років тому
I can vouch for the fact that water in plastic pipes & small plastic tanks ( such as shower units ) are capable of giving you as nasty shock, as this happened to our son when the element tank on our shower unit split. BTW good video, but please get yourself some decent trousers instead of those chavvy things, trousers befitting a man of your interllect
@markatherton7848
@markatherton7848 6 років тому
Would be interested to see this repeated with distilled water - think water cooled HV RF amplifiers...
@Madness832
@Madness832 6 років тому
So now what if you put the mains through it?
@jwflame
@jwflame 6 років тому
That will be discovered in the next video.
@randomj6188
@randomj6188 6 років тому
Hi JW. Could you possibly do a video regarding power factor? You always explain everything so well. Thanks!
@jwflame
@jwflame 6 років тому
Yes, that is on the list to do. Have not decided on the best way to do it yet, as power factor is a rather abstract thing to describe properly.
@randomj6188
@randomj6188 6 років тому
John Ward Well I'm sure you'll find a good way mate. You explain everything really well.
@andyxox4168
@andyxox4168 2 роки тому
@@jwflame best described mathematically ... 😉
@andyxox4168
@andyxox4168 2 роки тому
Pure water is an excellent insulator, what you have is not pure water ... water cooled stator bars in a 23kV turbo alternator perform very well with very low (electrical) leakage.
@nostorynow9350
@nostorynow9350 5 років тому
Deionised water does not conduct electricity. Water must have an electrolyte added for it to become conductive. By the way, it's not made of H2O either. May I recommend Peter and Pete's channel for demonstatrable proof of my statements. One may also learn more than one expects.
@ats-tj9rc
@ats-tj9rc 2 роки тому
1.2milli amps of current...? I guess you are saying that it is safe for me to use my 230volt electrical equipment with my acrylic bath with my plastic H + C pipework. We all can put up with a little tingle!
@james10739
@james10739 5 років тому
I figure it is it's just how conductive
@wire54321
@wire54321 5 років тому
Yes
@AngDavies
@AngDavies 3 роки тому
Should probably be tried with hot water too, conductivity is noticeably higher as the temperature goes uo
@andyxox4168
@andyxox4168 2 роки тому
😂😂😂 ... really?
@AngDavies
@AngDavies 2 роки тому
@@andyxox4168 yes, typically a few percent higher per degree C. For very pure water it's more dramatic, where it increases by a factor of 80 going from 0 to 100 en.m.wikipedia.org/wiki/File:Conductivity_of_Pure_Water.svg
@MarkGovier
@MarkGovier 6 років тому
Fresh water is relatively "safe". Next try it with brackish or salt water...
@sean999ification
@sean999ification 6 років тому
Shed catflap. Nods of approval all round.
@siux94
@siux94 6 років тому
So, how faulty boiler heaters kill people than? Distance Is significantly more than 1m, and voltage 220V? Thanks
@MrDubje
@MrDubje 6 років тому
I started wondering about the electric shower heads, like the one bigclive took apart. They specify the water hardness, though.
@sbusweb
@sbusweb 6 років тому
+siux94 You'll need to describe situation better?. Immersion-heater with ground not attached properly, maybe?
@H4zuZazu
@H4zuZazu 6 років тому
No, it would just trip the GFI/RCD. In Germany we have Electric Tankless-Waterheaters, they run with 400V (sometimes 2 phases or 3 phases depends on Wattage) and the Heating Elements are blank inside the Water after each Heating Channel comes a Insulation Channel. They don't even trip the RCD. The only downside they have is that they are sensitive to Air-bubbles in the water, wich can cause to burn through the heating wire.
@siux94
@siux94 6 років тому
I'm talking about non-modern water heaters, where heater is directly on the water, plus old style fuses without rcd. Answer is probably surface area + some capacitance which allows current to flow. Maybe metalic pipes also conduct majority of electricity.
@haczyk84
@haczyk84 5 років тому
add salt to this water ;)
@TheCorrectionist1984
@TheCorrectionist1984 5 років тому
Use deionized water next time
@TonyTony-xj6uv
@TonyTony-xj6uv 2 роки тому
OK hook one end to mains voltage hold the other end and with your other hand earth yourself if you believe your words
@stuc.6592
@stuc.6592 6 років тому
"So I've filled the pipe with water" would have sufficed! :-)
@Jamal_Tyrone
@Jamal_Tyrone 6 років тому
That was a bit of an odd test...
@farerse
@farerse 6 років тому
why doesn't the resistance decrease with more voltage applied?? ohms law and plastic water pipes don't go together?
@josjong5522
@josjong5522 6 років тому
The resistance of a resistor is not dependent on the voltage. Due to ohms law, of course, the current will change with the voltage.
@piotrliszka8481
@piotrliszka8481 6 років тому
Why would resiscance decrees? Resistance in this case is constant as pipe is not a potentiometer. Also ohm law does apply, because when the voltage increase, the current increases as well.
@farerse
@farerse 6 років тому
right I got it now .. rookie mistake from me lol
@iamdarkyoshi
@iamdarkyoshi 6 років тому
You guys have pretty weak water pressure, I'm used to about 6 bar here in the states...
@2100Warzone
@2100Warzone 6 років тому
That's because we worked out how many extra water leaks you get at 6 Bar. Not only do you get more leaks you get far more water wasted when a leak happens.
@jwflame
@jwflame 6 років тому
It depends on where you live. The minimum allowed is 0.7 bar, but typically it would be in the range 2 bar - 5 bar. Water companies generally go for the lower end, as it reduces the amount lost via leaks.
@dusterdude238
@dusterdude238 5 років тому
iamdarkyoshi: how does "Bar" in the UK translate to "PSI" here in the states?
@westwonic
@westwonic 3 роки тому
@@dusterdude238 1 bar = 14.504 pounds-force per square inch
@DerekHundik
@DerekHundik 5 років тому
pure water is not conductive at all. So the question is how contaminated our tab water is ?
@andyxox4168
@andyxox4168 2 роки тому
Fortunately our tap water is ‘contaminated’ as drinking pure water is not healthy and could kill you!
@DerekHundik
@DerekHundik 2 роки тому
@@andyxox4168 if its pure water you can't call it drinking water.
@andyxox4168
@andyxox4168 2 роки тому
@@DerekHundik … I’m not sure I did 🤔
@PGtips2691
@PGtips2691 6 років тому
All this achieves is to demonstrate basic ohms law. Resistance doesn’t change with applied voltage. Very very DANGEROUS comments at the end, THAT water in THAT pipe may have a set length and cross section but that won’t be the case generally. A series resistance with a human doesn’t guarantee safety when a voltage is applied, the critical parameter is current, and anything more than about 25mA can be fatal.
@toddbod94
@toddbod94 2 роки тому
No
Using a TT earth where a TN earth already exists
23:49
John Ward
Переглядів 70 тис.
How to Join Plastic and Copper Pipes | Plumbing Guide for Beginners
11:52
Мама и дневник Зомби (часть 1)🧟 #shorts
00:47
DO YOU NEED TO EARTH BOND PLASTIC WATER PIPES?
6:08
eFIXX
Переглядів 119 тис.
Types of Earthing System for Electricity Supplies (UK)
18:00
John Ward
Переглядів 461 тис.
AC, DC and Polarity in Electrical Systems
11:09
John Ward
Переглядів 44 тис.
Loop Impedance
15:56
John Ward
Переглядів 283 тис.
BONDING PLASTIC and COPPER PIPEWORK in ELECTRICAL INSTALLATIONS
8:31
LEARN ELECTRICS
Переглядів 7 тис.
Types Of RCD
20:06
John Ward
Переглядів 55 тис.
Earthing Systems for Outbuildings
17:44
John Ward
Переглядів 186 тис.
Earthing & Bonding - Part 1 : Earthing
24:56
John Ward
Переглядів 186 тис.
I had no idea SHEIN sold PC parts…
27:10
Linus Tech Tips
Переглядів 1,5 млн
Как часто вы чистите свой телефон
0:33
KINO KAIF
Переглядів 836 тис.
Сомнительно... Ну Окэй... Распаковал Nothing Phone (2a)
16:19
РасПаковка ДваПаковка
Переглядів 56 тис.
Нужен ли робот пылесос?
0:54
Катя и Лайфхаки
Переглядів 803 тис.