What is the Difference Between a Short Circuit and a Ground Fault?

  Переглядів 413,514

Electrician U

Electrician U

День тому

Join this channel to get access to perks:
/ @electricianu
Troubleshooting can be one of the most daunting tasks an electrician can face. There are usually just so many variables to consider when trying to figure out what went wrong or when something isn’t working. In todays episode of Electrician U, Dustin answers a follower’s question regarding the difference between Short Circuits & Ground Faults and the values you should see on your multimeter when testing for them.
🤘⚡️MEMBERSHIP⚡️🤘
JOIN ELECTRICIAN U - become a member and get:
FREE Continuing Education every year
FREE Practice Exams
FREE Monthly Video Courses
FREE Weekly Live Instructor-Led Classes
FREE Monthly Educational Newsletter
Premium Members-Only Content
Private Discord Channel
Monthly Members-Only Discord Chats
Sign up here --- www.electricianu.com/electric...
🎧🎹MUSIC AND VIDEO:🎹🎧
/ descantmv
🎬✍️ART AND ILLUSTRATION:✍️🎬
www.daverussoart.com
While the terms Short Circuit and Ground Fault seem to be used frequently and interchangeably, they are in fact quite different from one another. Think of a Short Circuit as a Short Cut, removing the load from the equation, and providing a path for the circuit to make its completed loop to the source of power. By doing this, it generates more amperage than the breaker is rated for, and the breaker trips. A ground fault is simply where a hot conductor has come into contact with something that is specifically grounded (maybe the grounding conductor itself or the case of a piece of equipment that is grounded, or a box/conduit that are grounded) and providing a return pathway to source. Either way, both of these scenarios happen BEFORE the load and in doing so, result in much higher amperage than the breaker is designed to withstand so it trips.
A great way to diagnose your power issues is to use your multimeter. There are two functions of said multimeter that would be helpful in this situation. You could use the OHM setting to check for resistance in the circuit. However, if you did not know the EXACT wiring of the circuitry, this would not be the most helpful of the functions. If you were to check between a hot and a neutral, you would most likely get the same values as checking from hot to ground. This happens as the grounding conductor AND the neutral conductor are run in the same conduit and have roughly the same length. A better choice would be to use the continuity function of the multimeter. If you are measuring before the load, you should not have continuity between the hot and either ground, neutral, or another hot. Once you figure out which two wires are completing the circuit, then you have found your problem!
Another great journeyman’s tip when troubleshooting is to gather as much information as you can about the situation and find out as many KNOWNS as you can. How much amperage is it supposed to draw? Has it done anything like this before? What exactly happened when it faulted (was there a shower of sparks, or a loud boom, etc.). A great one to ask is “did anyone perform any work on it recently? And if they did, are those folks available to speak? If something used to function, someone performed some type of work on the system, and now it doesn’t work, usually means the malfunction is either located within the work they did or is a direct result of the work they did. So, be a detective of sorts and gather as much information as possible. Use those KNOWNS to mark off the UNKNOWNS and it will narrow down the areas you will be looking in. It is also helpful to pull back and get a higher altitude look at the situation, then dive down into the details. Doing this in multiple areas of the whole system will help you eliminate possibilities, so you aren’t chasing demons throughout the entire system!
Also, remember that breakers don’t just randomly trip, and fuses don’t just randomly pop! There is a reason that they do. So, it isn’t prudent to just attempt to continue cycling the breaker until the equipment stays on or replace the fuse with a higher rating (or bypass the circuits protection entirely!). Something has happened and the breaker/fuse is just doing what it was intended to do! The appropriate action would be to diagnose the problem and then correct it!
We hope this has been helpful in understanding the difference between a Ground Fault and a Short Circuit and given you some useful information for troubleshooting an electrical problem. Please continue to follow Dustin and Electrician U as we are constantly updating our content to assist our followers in becoming the best electricians that they can be.
#electrician #electrical #electricity

КОМЕНТАРІ: 331
@igintell7295
@igintell7295 2 місяці тому
I'm a green maintenance tech and this video helped me out a lot.
@atmacm
@atmacm Рік тому
I’m glad you made this video. You’d be surprised how many electricians don’t realize the difference between ground faults and short circuits.
@Sparky-ww5re
@Sparky-ww5re Рік тому
If your having trouble finding if you have a ground fault or short circuit, and tried removing appliances, turning wall switches off with no success, then you know the problem is within the building. Because grounds and neutrals ultimately end up at the same place in the main panel, what you might consider doing is removing the neutral of the problem circuit from it's bus bar, then check if you have continuity between the hot coming off the breaker and the neutral. If you don't, but you have continuity between the hot and ground bus, you narrowed it down to a ground fault. In either case, ask yourself, what circumstances changed? Ex. an electric heater was being used for an extended period, and you smell burned plastic near a receptacle, see wisps of smoke, and now the breaker won't hold. Perhaps you heard a pop or crackle, or seen a flash, before the breaker tripped. You narrowed it down to a ground fault in the building wiring. Upon pulling devices upstream of the space heater location, you find a wirenut had burned off the hot wire and is touching the metal box. Not all troubleshooting is going to be so simple and logical, but you get the idea.
@dmeemd7787
@dmeemd7787 Рік тому
This is good stuff, you don't have to be in the electrical trade to need to learn the stuff I understand it, which is what I appreciate about this channel. People have trained in HVAC, I have sent them your way to do some homework. Videos like this being a perfect example, because I tell everyone, if you're not putting in time off the clock as well you're never going to succeed or learn what you need to learn or need to know
@josemartinez-jt6tw
@josemartinez-jt6tw Рік тому
Im in hvac and struggle electrical n using my meter
@that1electrician
@that1electrician Рік тому
@@josemartinez-jt6tw Buy some textbooks. See if your job will cover a few semesters of trade schools. I know a lot of employers do. That's how I got through trade school and got my certs. I wouldnt be where I am today if I didnt put my head to the ground and go for it.
@raymondgarafano8604
@raymondgarafano8604 8 місяців тому
YUP ppl who like this, their mind will absorb any info when they work on projects, sort of like seeing twine broken on motor windings, it is quite likely there will be a discoloration of the windings. even from years past seeing discolored coils in a motor or gen you'll remember the twine was most likely broken leading to the fact the coil overheated and a good chance there will be a shock hazard.
@MakeNoise280
@MakeNoise280 11 місяців тому
Remember when testing resistance or continuity remove power or turn off power. Thanks for the info, helpful.
@pdk79
@pdk79 Рік тому
Prior to continuity check, It seems a very important step is to disconnect the device from the supply neutral (and hots) otherwise the bonding at service panel will not allow you to differentiate between neutral and ground.
@maar5725
@maar5725 11 місяців тому
You'r Right .
@Stones_Throw
@Stones_Throw Рік тому
An excellent explanation. I would have only added the step of unplugging/disconnecting the load from supply wiring to isolate and narrow down possible causes.
@colinstu
@colinstu Рік тому
"Finding the knowns" … yeah, that's an amazing troubleshooting step - and applies to all kinds of stuff including outside electrical. I can't tell you how many times someone asks for help only to find out they skipped all the easy stuff to check, didn't "look for the knowns" and is struggling off in some completely unrelated area because of it. I always step ALL the way. back, start from the beginning/scratch, and yeah, go thru all the knowns and go from there.
@desertodavid
@desertodavid Рік тому
@Colinstu by "knowns" are you talking about "probable faults" in a circuit?
@colinstu
@colinstu Рік тому
@@desertodavid it's talked about in the vid. But no, basically starting with the basics, starting with the baseline. You need to start an investigation by starting with the basics, and finding out the most basic parts of the situation. It can be easy to be carried away jumping into a situation going off of what other people have said, only to find out they missed something SUPER easy / simple because they skipped the basics and went right into more complex situations. (or you yourself doing the same thing. "I am so smart, it MUST be this instead of like… checking breakers, checking how the wires are connected, tracing them out, etc. A bad assumption can send you down a totally wrong path. You may end up with the final solution anyways - but all that could be skipped if the basics/knowns of the setup are determined first.
@desertodavid
@desertodavid Рік тому
@@colinstu nevermind. Obviously you don't know what I mean by probable faults. I'm an experienced Electronics technician, so save your time.
@colinstu
@colinstu Рік тому
@@desertodavid oh, PROBABLE, I read that as "ground" (as in ground faults). Yeah that's definitely all part of it.
@JohnThomas-lq5qp
@JohnThomas-lq5qp Рік тому
I'm a retired sparky with over 50 years in this great trade. Several times I have came out and found that a circuit breaker trips as soon as you turn it on. Unplugged everything & turned every switch on that circuit off and problem did not go away. Could not pick up and grounds on either of my VOM'S. Used my expensive Fluke combination VOM/ Megger. Did not pick up a ground at 50 volts but got a low resistance reading using 100 volts. One of these was caused by water that halve filled an outdoor receptacle box. Another time old rubber insulated wire had broken pieces of insulation allowing two wires maybe seperste by a hair. If I had 10 devices on a circuit would try to guess middle point and disconnect wired then flip the breaker.
@keltonfoster
@keltonfoster Рік тому
Man the way you explain it makes me understand it much better, thank you. That mentor you had is the man. Knowns is what will help you pin point the issue.
@FR3ERUNN3R
@FR3ERUNN3R 9 місяців тому
Needed this today. Came across someone’s shoddy work and just immediately stressed out when I opened the j-boxes. Hopefully when I go back on Monday I can solve my problems.
@JCWren
@JCWren Рік тому
This should be obvious, but never test continuity on a live circuit, e.g., using the meter in continuity mode across hot and neutral, hot and ground, or hot to hot (for 220V). A Harbor Freight quality meter will be destroyed, a good meter will blow the fuse. While electricians don't typically use this, but there's a device called a Time Domain Reflectometer. It fires pulses down the line, and measures the return times. It can find shorts, changes in resistance, and open circuits. You can also measure the length of the wire if you know it's velocity factor. They're not crazy expensive, but they're not cheap either.
@Sparkeycarp
@Sparkeycarp Рік тому
We had a job subbing for a company that had a contract to move all the service meters from the panels on the sides of mobile homes to pedestals in the front corner of the houses. They ran all the new supply lines under the houses to the main panels. Our job was to solve all the ground to neutral faults in the whole park. As well as replace some very old or under rated panels and any other problems. I did all the troubleshooting with my apprentice helping. We had to open and disconnect a lot of wire nuts. First thing we always did was pull the electric dryer cord. A lot of those are neutral bonded to ground. Keep up the great videos. Still learning and finding better ways to explain things to apprentices and customers. Even though I have my own company now.
@berthongo8531
@berthongo8531 Рік тому
We would get sent out to work on a customer's turbine with a "known" issue. That is, until we got on site and found that the customer's "known" issue didn't make sense. I finally figured out that the best thing to do was to start shooting the breeze with one of the operators and find out what they were trying to do when the "known" issue popped up. It usually had nothing to do with what the office people said it was. It usually also pointed out that they did something stupid or that something else on site caused the issue to begin with and the turbine was collateral damage. Really cut down on the troubleshooting. Know your knowns. I like that.
@Hvn1957
@Hvn1957 Рік тому
This is SO true. We tell all out clients, very politely, to just describe the problem without any speculation. Of course, if someone spilled their coffee on the control panel, I’d like to know that too 😏😏.
@jacobplank
@jacobplank Рік тому
Thanks for the great video!! Definitely helpful in understanding it. I do use continuity alot for troubleshooting. Have an outside project (still not finished) alot receptacles In the yard where over time got covered over with dirt and multiple shorts in the circuit, I take sections at a time and test continuity and finally figure out where and which wire. It's been a nightmare job and still a few left to do.
@williamcash4126
@williamcash4126 Рік тому
i am a master electrician and hvac tech over 30 years .I am disabled now .Everything you said is correct .the first thing l was taught about electricity is it all ways looking for the ground and you don`t want to be the best way to it! all ways turn the load off before turning on power!Because a loose connection under a load is the same a welder. it heats up and makes a bigger gap and bigger arc every time load comes on! and a breacker matches the size wire to protect the wire from heating up and burning!The nuetral is the designated path to ground and it just as hot as the power wire under a load!
@ryanhoffman5864
@ryanhoffman5864 Рік тому
Dustin, could you please do a video with tips and tricks to troubleshooting with both a multimeter and a clamp meter? I’m an industrial electrician that’s been with my company for a year, and I’d like to get into service calls and learning how to use my meters to help with troubleshooting. Love your videos, and I would appreciate it a lot. Thanks in advance if you do this.
@gp3646
@gp3646 Рік тому
Trouble shooting with a clamp meter? Are you talking about an amp probe?
@repro-rt6lu
@repro-rt6lu Рік тому
I do industrial as well 3y in....I believe it's a fluke 375 that measures in rush.....I'm wondering if I clamped the neutral close breaker and got a inrush value turned around and did the same for ground how they would compare...the expectation is to try and catch the one drawing excessive current to determine short circuit or ground fault...
@Willeeum8293
@Willeeum8293 Рік тому
@@gp3646 amp clamp
@jones0618
@jones0618 Рік тому
Be prepared to be humbled. Service work and troubleshooting is a whole different animal than commercial/industrial new construction. But it will be good experience for you and I highly recommend every apprentice down both new construction and service work. I'm a journeyman and still struggle with troubleshooting at times and using my meter. When you install for awhile and do nothing but bend pipe you get a little rusty when you actually have to think like an electrician. Hell just last week I had to look up how to calculate a lighting load using ohms law. I had brain dumped all that and haven't done a calculation in God knows how long.
@lyokss
@lyokss Рік тому
I had the opportunity of being present when a 480v/1200a breaker was constantly tripping and it was a sight and sound to experience. It was an ice maker for a food processing plant, and the reason it kept tripping was too much in-rush current when the control system fired up the compressor(s) soft starts. I just needed to increase the breaker in-rush settings, so I learned some troubleshooting techniques that day.
@miguelsword9611
@miguelsword9611 Рік тому
Very informative. He clearly knows his business. Excellent presentation.
@joeyc5564
@joeyc5564 Рік тому
My trade school just uses you videos to teach us ⚡️⚡️
@dmz6973
@dmz6973 Рік тому
This video is like the gold rush, because I'm finding lots of gold nuggets in here! Thanks for the great info Dustin!
@Jaxemus
@Jaxemus 5 місяців тому
This video helped me fix a lighting issue , thank you!
@Sembazuru
@Sembazuru Рік тому
There may not be "continuity" as defined by your DMM when a device is turned on. This is because the continuity feature of DMMs beeps below 1-2 ohms. But the actual load may be hundreds to hundreds of thousands of ohms. That said... __NEVER__ use the ohms/continuity reading of a DMM on a live circuit. You'll either blow a fuse in your DMM, damage your DMM, or explode your DMM (depending on the voltage across your DMM leads when you take the reading and the safety features inside your DMM).
@michealplater9007
@michealplater9007 Рік тому
Yes, you are correct regarding continuity. I have seen electrician's test with a meter, its open circuit. No, your meter has a maximum of 2k, anything over this will show open circuit. You need to read the meter manual and understand its limits.
@atmacm
@atmacm Рік тому
On flukes the continuity setting is usually below 80 ohms
@stevenfoust3782
@stevenfoust3782 Рік тому
I like when flames come out of the breaker when you reset it and your hand is on the breaker along with a nice pow.
@trentthompson5734
@trentthompson5734 Рік тому
I'm in hvac but we do some of our own electrical. Making me a better tradesman. Thank you
@arthurburke3771
@arthurburke3771 Рік тому
Fantastic job on explaining how to troubleshoot a circuit issue! Many times the first thing people think is that it must be a wiring problem without considering the possibility that it could be something running off the circuit.
@zacharyhottell8251
@zacharyhottell8251 Рік тому
Make sure the power is off. Disconnect the wiring to speed things up. Remember you will a always read continuity or "ohms" over a coil such as a heating element but you should more resistance over a coil then a derect short.
@banggugyangu
@banggugyangu Рік тому
This was an excellent video with wisdom that applies to fields far outside of just electrical. Great troubleshooting advice for all troubleshooting.
@cecillec2331
@cecillec2331 8 місяців тому
Thank you very much for the great explanation.
@lalmuanpuiamizo
@lalmuanpuiamizo Рік тому
Nice demonstration. Unplug/disconnect then probe to isolate to see which side of the circuit... zoom in. That's how I do
@cadillacphilli
@cadillacphilli 5 місяців тому
I love your channel, you are awesome! Very helpful and you explain in a way that a less experienced person like myself can understand. Thank you so much for being here. Kind Regards. Philli.
@kamakaziozzie3038
@kamakaziozzie3038 Місяць тому
something to also keep in mind. Ground faults are not only created by hot conductor(s) touching metallic frames or equipment grounds. I do a lot of outdoor lighting troubleshooting and can’t tell you how many times tripped GFCIs are caused by junction boxes located in the soil that have moisture contamination. Enough current is able to find its way to earth ground that it trips.
@donmoore6931
@donmoore6931 Рік тому
Dustin. Very helpful. Question: It is necessary to de-energize a circuit before you test for continuity, yes? Were you assuming that with a tripped breaker, the circuit is by definition de-energized?
@tedtenny
@tedtenny Рік тому
Good way to destroy your meter when checking for continuity if you did NOT DE-ENERGIZE your circuit! Continuity testing or resistance, (same circuit within the meter) relies on its own internal power.
@matthewblankowski2265
@matthewblankowski2265 Рік тому
This connected some really important dots for me. Thank you.
@ThommyGunnGaming
@ThommyGunnGaming Рік тому
Great video! Wish I saw this last year, had a similar issue and did all kinds of troubleshooting to figure out it was a simple fix in the junction box, felt dumb. BUT hey, I have a random question, as a DIY homeowner, I have a couple spots I need to run new Romex to where the existing is 12/2 and I need 12/3. Talking to people I work with they all make it sound so simple, attach the new to the old and pull through DONE. Wrong, because from what I know and, in my situation, the installers staple it to studs in the wall. So how does a professional replace Romex in a finished wall? or do you cut open the wall, patch it up, and paint when done? Trying to avoid that, but it might be my last option. Thanks, appreciate the easy-to-understand info.
@until11
@until11 Рік тому
I've always used the term ground fault to refer to an issue that happened on a switched return circuit.
@hliz8818
@hliz8818 Рік тому
When checking continuity you have to turn off breaker right? So you dont damage your multimeter..?
@watertech011
@watertech011 3 місяці тому
Great advice on gathering the "knoiwns" , in the process you will get to the problem.
@traditionaltools5080
@traditionaltools5080 Рік тому
True, sort of. You can have a ground fault with as little as a few milliamps of current. Often from a small cut or break in the insulation and often intermittent. That's why it's so important to megger new installations. Especially if you're using conduit.
@TonyParker-lh5ct
@TonyParker-lh5ct Рік тому
thank you for the explanation. The ways to explain this was some simple. 💯
@ericksonfilpo1604
@ericksonfilpo1604 Рік тому
You have to be the best instructor in the world, thanks for your video
@christophermiller8075
@christophermiller8075 7 місяців тому
Keep up the great explanations!
@michealplater9007
@michealplater9007 Рік тому
99% of the time it's not the wiring, it's the equipment connected. Disconnect the equipment and check if the breaker will reset. Depending on the fault a multimeter may not show the fault and an insulation resistance tester (Megger, trade name) may be required.
@iwenive3390
@iwenive3390 8 місяців тому
90% of the time it’s a loose wire in the breaker
@lyricalnatty
@lyricalnatty 7 місяців тому
I know what you mean about checking 'the knowns ', I'm a heating engineer, work on boilers and stuff. When I get a call out, cos someone's heating is not working. The first thing I do is find out if their gas meter is topped up, (a lot pay as you go customers in London), so yes you right, check the knowns ; simple things like checking to see if there is gas flowing on cooking hubs in the kitchen. You will be surprised how many times that's the case: no gas.😊, Another thing, always let the customer tell you what happened. They may already have diagnosed the problem for you.
@joelniimensahafoteylewis4475
@joelniimensahafoteylewis4475 Рік тому
hi Dustin, can you make a video on the complete tutorial of the multimeter, as in how and when to use certain button.. on it ?
@phwlee
@phwlee Рік тому
Great video. Very informative. Which model multi-meter is the one in the video? Looks like maybe the MM720
@unrachna
@unrachna Рік тому
Thanks for your teaching!❤❤❤
@kevindick7485
@kevindick7485 Рік тому
Nice job . However it may be to make sure all power is lock and tagged out if possible and no live power going to the circuit you are checking for continuity . I saw a guy in class one time blow up his meter because he did know to have no power when checking continuity . A little tid-bit for your next presentations. I can not stress the one little thing like that you did not mention !
@normanromero719
@normanromero719 Рік тому
Yup!
@Kaiser.Alexander.I
@Kaiser.Alexander.I 2 місяці тому
The best from the video was with the knows! It’s a life reminder.
@BlackHoleForge
@BlackHoleForge Рік тому
Hey when I was in college studying networking, we had a tool called a Fox and Hound. It sent a signal Through the Wire, and you could pick it up with a handheld device. Is that possible for electrical wires? Like if the wire did find a shortcut, could it be used to find where the shortcut is?
@knjava9793
@knjava9793 7 місяців тому
So can you do a short video on the square d qo120PAF breakers and their service light codes? Service light flashes when I turn on breaker but no tripping occurs when we use all the outlets/lights - everything works fine but likely isn't as the light is flashing. Called Schneider support and they were no help
@UpperAquatics
@UpperAquatics Рік тому
Thanks for the video! I'm studying for my aptitude test to join IBEW. I know this isn't going to be on the test but its helpful to know for the interview and boot camp. Anything I can do now to get a leg up is helpful.
@quietlyloud7767
@quietlyloud7767 Рік тому
Good luck im in IBEW and it’s great
@JustinLorenzo63
@JustinLorenzo63 Рік тому
Keep doing videos like this,I really appreciate them
@randtemple2332
@randtemple2332 Рік тому
I use a light socket. Black from pigtail goes on breaker and neutral goes to the load. Short or ground fault circuits will cause light from bulb. When fault is cleared light goes off
@akamomakawife4928
@akamomakawife4928 Рік тому
Thanks for your time an videos iam sure I have a short going on with my dryer now got to find it but u save me with this video ty.
@milesharlan1
@milesharlan1 Рік тому
Dustin, Thank You ...Another great learning tip!!
@johnmaranuk1842
@johnmaranuk1842 Рік тому
Dustin, you're awesome! Experience comes from years on job. We always learn everyday. No way we can know it all. I was taught at early age, "we stop learning, when we allow ourselves to not want to take anymore in". Best tip to apprentice is, do not say ya know, if ya don't. Always ask questions, its better to ask the 'why' , then to just keep doing, cuz you're told so. That will show interest in trade and jman will appreciate it ( well, most would, lol). Cheers from Pennsylvania!
@jmrgoldable
@jmrgoldable Рік тому
Thank you so much...knowledge is power!!
@CH-dr7nm
@CH-dr7nm Місяць тому
A lot of light fixtures will give you continuity between neutral and hot conductor you always got to keep that in mind as well when troubleshooting
@waynegram8907
@waynegram8907 Рік тому
DUSTIN, A Ground Fault is considered the Hot wire is directly connected to the Green wire Ground? a Short circuit is considered if a piece of the equipment's internal wiring or internal load is shorted from hot to neutral or the load is shorted from hot to chassis? How I would troubleshoot a ground fault or short circuit is shut off the breakers then disconnect the Hot, Neutral and Ground wires to the load/equipment, then use my DVM meter to test if the wires are shorted or if the equipment/load is shorted. This method is better because you can diagnose if the load/equipment has an internal short circuit or an internal wiring ground fault. If you don't disconnect the H,N,G wires and multiple pieces of equipment/loads are on the "Same Branch/Same Breaker connected "in parallel" you will be guessing, because a short circuit and ground fault will measure both the same in "milliohms". What is even worse to troubleshoot when you have a short circuit that crossed over in a wiring harnesses in the wall or internal inside a piece of equipment/load to another wiring harness that is on another breaker which you will have "leakage current" or Ghost measurements". This would be a good video lesson about "ghost measurements" and leakage currents.
@BobSmith-vq3uo
@BobSmith-vq3uo 5 місяців тому
Great teaching. Thanks for sharing this.
@spark5558
@spark5558 Рік тому
Thanks for the advice
@rmcq6287
@rmcq6287 Рік тому
nice to hear someone talking that knows what they are saying.... lol.... thank you for what you do!
@alejandroquinones5439
@alejandroquinones5439 Рік тому
Dustin, could a grounding cable physically go up a structure (let's say 8 ft.) and then be routed downward towards the ground?
@mariannebest2536
@mariannebest2536 Рік тому
You mentioned that you should never have continuity between a hot and a ground..I agree with that on an appliance, however, it can tone out with lightbulbs sometimes. Can you touch on that and explain it?
@user-vn8hq7ot4k
@user-vn8hq7ot4k 10 місяців тому
Dude gotta be my favorite sparky to watch
@brianmcdermott2430
@brianmcdermott2430 7 місяців тому
Great info. Thanks.
@vicferrmat4492
@vicferrmat4492 3 місяці тому
Thank you, I was trying to understand this for some tìme.
@seankaran3490
@seankaran3490 Рік тому
Excellent video. Thank you!
@network_king
@network_king Рік тому
If you do the breaker thing just make sure the circuit is turnded off if doing continuity. Usally when i try to diagnose somehting I start as close to the source as i can and or the simplist to get to. I hade a table was that was acting odd for a bit then just stopped turning on. I tried a few different outlets played with the internal breaker, switch. I then unplugged turned on checked continuity to between the hot and neutral was open. So then tore into the switch, breaker, checked the cord they were all fine. That pretty much left the motor, checked that open circuit, checked from each line to each brush one was open so figured either a winding failed, thermal cutout, or maybe a bad connection. Ended up tore apart was a loose spade terminal on the brush holder fixed good as new. I'd do similar for something like this remove anything that would show like a load then start from source and work back until you find somehting that seems off.
@bencoss7003
@bencoss7003 6 місяців тому
The gentleman is right, correct terminology on the job gets the job done correct and efficiently, and when you have those two it means that you done the job safely to, German if you ever do any job that has anything to do with electricity what you got to remember is your multimeter so you could test before you start, and the best way to find any problem in an electrical circuit is the start where your source comes in and follow it out.
@paulnormandy6247
@paulnormandy6247 Рік тому
Could you unplug everything on that circuit breaker and plug them back in one at a time to identify which appliance is causing the fault?
@Sembazuru
@Sembazuru Рік тому
This is a perfectly valid troubleshooting technique to narrow the fault down to a specific appliance or identify if the building wiring is the fault if the fault still shows with everything unplugged/disconnected.
@garyme7201
@garyme7201 3 місяці тому
Dustin, what are the steps to find a partial short in an a/c circuit? I have a multiple outlet circuit along with a garage opener. The garage opener motor burnt up and is disconnected. The circuit now has a low voltage of 46 volts. Gary
@sumofool7399
@sumofool7399 Рік тому
Good stuff Dustin, would love to see some more 3 phase 480V troubleshooting videos as an industrial electrician I would love to hear your take ! Keep pumping out this great content love it
@llanbull
@llanbull Рік тому
I got a question, how do you find a good ground when testing a panel or machine. Like which place is best to put the black lead of the tester if there is no obvious ground screw? I was testing a micro switch and I failed the exam bec. I can't find a good ground in the machine. Bec. normally you put the black lead on the ground and the red on the circuit you gonna test to find the voltage.
@AnthonyReviews-uc5ip
@AnthonyReviews-uc5ip 6 місяців тому
Hi there. When installing a neutral wire in an old house. Is it ok to install a single wire or do you have to grab the entire shielding of the romex and cap the black wiree?
@onradioactivewaves
@onradioactivewaves Місяць тому
Best practice would be to always cap off wires, even if they aren't connected to anything. They can become energized due capacitive or inductive coupling, or even touch something live.
@MJQuintana
@MJQuintana Рік тому
Great and on-point!
@cjvillarreal217
@cjvillarreal217 Рік тому
Dustin, I work in the cable communications field. I commonly come across voltage on the ground wire of the house. Often times it causes our 18 awg coax cable to melt. Is this considered a ground fault? What are some ways that I can test for this issue to show the customer that it’s an issue with their electrical service? Us as cable technicians seems to always catch the blame. Thanks in advance!
@ChristianRamosELCRVEVO
@ChristianRamosELCRVEVO 6 місяців тому
Ok I see what you did between hot and neutral. Can I test each conductor to ground? Like test for continuity to see if 1 of the wires is going to ground?
@freddesgarage
@freddesgarage 7 місяців тому
Hi! I have a Hyundai Tucson 06 with a irbag light on,scanner states B1326 code (FIS) Front impact sensor short to ground Drivers side. How would you trubleshoot this? Thanx in advance //Fredde
@josephnicolas2158
@josephnicolas2158 Рік тому
Amazing video as always!
@user-hs5vf3wi8e
@user-hs5vf3wi8e 5 місяців тому
Hoping for info regarding testing continuity from an alternator. If I test across positive terminal on alternator to positive battery terminal I get a steady tone (beeeeeeeeep) and then when I test from alternator POS to ground I get a consistent broken tone (beep, beep, beep...). I ensured that both leads are making good contact at all times. Any idea what is happening with the broken beep? Thanks for any help.
@turrubiartes21ify
@turrubiartes21ify Рік тому
Can you please explain the difference between US voltage from European Voltage and give a brief history, on how we adapted the 120V 60HZ vs the 230V 50HZ. Can’t seem to find a video with good explanation, Thanks
@TheWickerShireProject
@TheWickerShireProject Рік тому
It runs back to the beginning of power companies needed to reduce copper and become cost effective. Europe adopted 220v to save on wire. Supply and use of power to a 220v is also cheaper. When Thomas Edison adopted the 120v standard the USA ran with it. Oddly Europe in its early days did use 120v. Unless specified by the manufacturer to operate on both 50Hz and 60Hz, appliances may not operate efficiently or even safely if used on anything other than the intended frequency. 60Hz runs hotter and 20% faster. This IMO needs to be considered when using Electric Motors.
@rm4305
@rm4305 9 місяців тому
Would Arcing just be another term to describe a short circuit ?
@electricalproblemsolve
@electricalproblemsolve 8 місяців тому
Thanks for your good information. i known that there is huge support my jobs. 😍😍
@DanielCojocaru-bt5ws
@DanielCojocaru-bt5ws 2 місяці тому
Good explanation
@electricaltyler5998
@electricaltyler5998 Рік тому
THANK YOU SIR I use the same technique to check if a motor is shorting phase to phase or to the ground
@John-pu5kz
@John-pu5kz 8 місяців тому
2 Types of Short Circuits Normal short circuit: In a normal short circuit, a powered or hot wire touches a neutral wire. Immediately, resistance drops and the current begins to move in another path. Ground fault short circuit: In a ground fault short circuit, a powered or hot wire touches a grounded section of a box, device, appliance, outlet, bare ground wire, or anything else supplied by the electrical circuit.
@kellyjaramillo9382
@kellyjaramillo9382 Рік тому
Can you do a video on fuses and what the interrupting rating means?
@jdjohnson2131
@jdjohnson2131 2 місяці тому
In commercial remodeling, we come in AFTER they screw something up, have a tripping breaker, but do not know the load, the correct neutral, etc. Knowing both sides makes it trivial.
@number1pappy
@number1pappy Рік тому
Off topic question and request....... I'm thinking about installing an "isolated ground" outlet for my home audio system. However, I don't see the point of an isolated ground outlet if the ground and neutral wires are connected together at the breaker box. Could you possibly do a video on this topic explaining how an isolated ground outlet is functional considering the ground and neutral are connected together in the breaker box. Thank you!!
@nomen_meus
@nomen_meus Рік тому
If your house is wired with NM (Romex) cable and uses plastic device boxes, you already have what is essentially an isolated ground system. The isolation is meant to be at the device, not the source (breaker box). If using metal device boxes, an isolated ground system uses separate grounding paths for the ground pin in the receptacle and the device mounting strap and metal device box. To help eliminate possible noise and/or ground loops in a home A/V system, plug all interconnected electronics into a single power source (e.g. a power strip).
@dennishall5659
@dennishall5659 Рік тому
Thank you for that, I forget about continuity. I have a old house with an old water heater and the breaker keeps getting tripped periodically. I have a home warranty that came with house and so I called and they sent guy out. Ended up changing 1 element but now 2 months later same issue. I'm not going to pay again to send same guys out so I'm going to see if I can figure out which one is broke or if another problem, thank you.
@fazman6218
@fazman6218 Рік тому
I am not an electrician, but want to learn to be one. You touched on an item about DVM. Can you make a video on how to use DVM's and what each of those dial settings does, how it will help me troubleshoot?
@TheWickerShireProject
@TheWickerShireProject Рік тому
Dustin I made a recent video trying to figure out an Aims Inverters Meaning by a Floating Neutral. I ended up coming to the idea I HAD to unbond my neutral to ground by removing the GREEN bonding screw in the Mains panel. It was in my mind the only way to achieve this. Anyone here is free to advise on this topic and look over what they mean by " Warning! Do not bond the neutral to ground. This may or will damage the unit." I am off grid. I have been using the inverter in RV application but I will Need to wire it for a grounding rod as my Tiny home needs better protection and my loads will increase. Again any one can suggest or advise a better wiring technique. I'm out of options. I got to this point after exhausting my limited DIY knowledge. This is a very common thread on these types of inverters and has so many people in confusion. My system is a 6,000 watt 48v Aims low frequency pure sine with a Ground, L1 L2 in / and a L1 L2 N out. It has a case ground terminal block on the unit. There is a ( Looped ) set of of ground wires as well for a Mobile application. Once I use a Grounding rod for a more permanent install my neutral bond to ground comes into play. Please help my Mind is Grounded out! heh Thanks!
@navidnikraz2299
@navidnikraz2299 Рік тому
Great explanation
@mlee81
@mlee81 8 місяців тому
Was camping, touched the metal electrical box to disconnect a cable. Felt a warm tingling sensation in my arm while touching the device. Pretty scary.
@juggerfox
@juggerfox Рік тому
So if the appliance is plugged in, but switched off, we should have continuity up to the point in the circuit where that on/off switch is, right? Like taking that simplified drawing of the washing machine, the red and black will have continuity until well inside the appliance, despite the appliance being switched off. Or not?
@Lalasoth
@Lalasoth Рік тому
No not normally. Every device is different though so ymmv
@niconine268
@niconine268 7 місяців тому
This is great. Kinda far above my grade. That's ok though. Picked up a few tips. Thank you
@mkidd8806
@mkidd8806 Рік тому
First thing I do is tune breaker on and if it trips immediately then I unplug(if it has a plug). Do the breaker and if it trips again then I KNOW ITS NOT THE PLUGGED IN ITEM. Then trouble shoot from there.
@larrygwinn6649
@larrygwinn6649 Рік тому
Hi, how do you find a ground fault. I've checked all connections and replaced wire nuts and receptacle
How to use a multimeter like a pro, the ultimate guide
12:55
James Gatlin
Переглядів 1,3 млн
What is the Difference Between Single Phase and Three Phase???
23:11
Electrician U
Переглядів 515 тис.
Підставка для яєць
00:37
Afinka
Переглядів 53 тис.
Won't These Melt?!? 15amp Receptacles on 20 amp Circuits!!!
11:47
Electrician U
Переглядів 1,2 млн
What is the Difference Between Grounding, Bonding and Neutral?
15:15
Electrician U
Переглядів 76 тис.
Overcurrent, Overload, Short Circuit, and Ground Fault
6:54
Dave Gordon
Переглядів 771 тис.
Fault Finding Electrical Circuits - Electrician Life
24:57
Artisan Electrics
Переглядів 369 тис.
Where Does Grounded Electricity Actually Go?
19:36
Practical Engineering
Переглядів 4,7 млн
The BEST Way TO Perform a Parasitic Draw Test
10:49
HumbleMechanic
Переглядів 4,1 млн
How To Troubleshoot Circuit Breaker Tripping & Testing
24:41
United Tradesman Academy
Переглядів 89 тис.
How to use a multimeter like a pro! The Ultimate guide
28:43
The Engineering Mindset
Переглядів 1,8 млн
Neutral Imbalance in Multiwire Branch Circuits (Two Hots, One Neutral)
16:41